Operation
ASD 531, Technical description, T 140 416 en
91 / 105
G80, AMB faults
001
Air pressure sensor fault
002
Temperature sensor fault
004
Undervoltage fault
008
Clock fault
016
Rotary switch fault
G81, Operating system faults
001
Mailbox unknown
002
Mailbox pool
004
Diverse
008
Timer
016
Mailbox memory enable
032
Buffer overflow option module
064
EEPROM
8.5.5
Operation and displays on the XLM 35
Fig. 45 XLM 35 operation and display
The two LEDs on the
XLM 35
indicate the communication state.
LED 1 (yellow)
State XLM 35 <> addressable loop (lights only if supply from AMB is OK)
Not lit
No addressable loop voltage
Continuously lit
Addressable loop voltage OK, no communication XLM <> Line
Flashes (normal operation)
Communication XLM <> Line OK
LED 2 (green)
State ASD 531 <> XLM 35
Not lit
No power supply from AMB 31
Flashes (normal operation)
Supply from AMB 31 OK, communication XLM <> ASD OK
XLM 35
L1
C1
G1
L2
C2
G2
LED2
LED1
LED 2
LED 1
A
M
B