Normal temperature
rating
75°C
Communication module
Nominal Voltage: 4V(+/-0.1V)
Maximum load: 1.4A (Peak)
3
Protection
Dielectric Strength
•
Withstands 415 VAC continuous
•
Impulse 10 kV @0.5 J in accordance with IEC/
/AS 62052.11
•
12kV @ 9J in accordance with latest NMI M6-1
4
Compliance
Reference Standard
AS62052.11, AS 62053.22,AS 62053.23,AS62056.21,
AS62054.21, NMI M6-1
Lighting Interference
AS62056.21 (16k Lux under controlled conditions)
Environmental
Protection
IP54 with suction
Protective class
II
5
Environmental
Storage Area
The meter is designed for indoor (/outdoor)* use, in
accordance with IEC 60721-3-3:1996.
*Ideally the meter should be stored and operated in a
dry, well ventilated, climate-controlled building. Rapid
changes in temperature and humidity should be
avoided.
Operating Temperature
as per AS standard
Range
Outdoor Meter
Specified operating range
-10 °C to +55 °C
Limit range of operation
-10 °C to +70 °C
Limit range for storage
-25 °C to +70 °C
Limit range for
transportation
-25 °C to +70 °C
Operating Temperature
as per NMI M6
Specified operating range
-10 °C to +60 °C
Limit range of operation
-20 °C to +70 °C
Limit range for storage
-25 °C to +70 °C
Limit range for
-25 °C to +70 °C