- 6 -
3) Instruction to Mounting
○
The exclusive mount for air pump installation made of concrete should be arranged.
The mount should be away from the foundation for at least 150mm and its height
should be min 100mm higher than the foundation.
●
Noise may be caused by vibration of the air pump mounted on an unstable place
such as concrete blocks, shelf etc.
○
Install the air pump on a horizontal mount taken a level after the concrete has
been completely dry.
●
Setting the air pump before concrete has been completely dry can embed it
therein.
●
The load caused by setting the air pump in a declining position may shorten the
life of the parts.
○
A ventilation fan should be put in a fence for water, noise proofing to keep
temperature inside the fence below 40
℃
.
JDK-150/200/250
○
When mounting the air pump at a place got wet heavily,
provide a roof or a fence to keep the air pump from
water.
●
Water taken in the air pump may enter the charged
parts, which could cause electric leakage, electric
shock or short circuit.
●
Ordinary rain will not enter the air pump.
Over 240mm
Over 180mm
Over 100mm
Hose Clamp 20A
Hose Clamp 13A
In application of VP13 pipe
In application of VP20 pipe