PrimeTest 300
Operating Instructions
- 96 -
Test Current
30mA rms sinusoidal
Test Duration
2000ms max
Pass/Fail Limit
None
Display Range
0 – 2000ms
Measuring Range
20 – 2000ms
Resolution
1ms
Accuracy
± 10%
15.8 IEC Lead Test
This is a 3 part test is made up of:
Earth Continuity – specification as 10.1 above.
Insulation Resistance – specification as 10.2 above.
Wiring Check – checks for:
Live open
Neutral open
L/N Short
L/N Reversed