ELECTRICAL

Surge Protection

For protection against damage caused by high voltage
surges, your motor has built-in surge protectors. 

NOTICE:

Surge protectors 

will not

protect against direct or

near direct lightning strikes!

GROUNDING

Permanently ground all electrical components in accor-
dance with the National Electrical Code and applicable local
codes and ordinances. Make a permanent ground using a
conductor of correct size from a grounded lead in the ser-
vice panel or a properly driven and grounded ground rod.

DO NOT

ground to a gas supply line. 

DO NOT

connect to

electric power supply until unit is permanently grounded.

If plastic well casing is used in your installation, ground the
metal well cap or well seal, providing electrical leads to the
pump motor go through the well cap or well seal. 

The grounding conductor need not be larger than the cir-
cuit conductors supplying the motor providing circuit con-
ductors conform to the wiring data provided in this manual. 

CABLE SPLICING 

NOTICE: 

Match colors of wires in cable to colors of wires

coming from motor.

For #14, #12, or #10 Wire Cable Installation 

Included in the splice kit are three plastic splice insulators
and four butt connectors; use two insulators on “2-Wire” mo-
tors and 3 insulators on “3-Wire” motors. The extra con-
nector is for the ground lead. The insulating sleeves can be
used on wire cable sizes #14, #12 and #10. No tape is re-
quired for this type of joint. To use the insulators stagger the
pigtail ends of the motor leads and the cable. Cut each lead
about 4" longer than the last one. 

Method #1: Soldering 

(Figure 6)

.

Stagger the pigtail ends of the motor leads and the cable. Cut
each lead about 4" longer than the last one. Trim the insula-
tion back 1/2" on each lead. Unscrew the plastic caps from
the insulator. Place parts on each end of the wire to be
spliced, as shown. 

Unscrew the plastic caps from the insulator. Place parts on
each end of the wire to be spliced, as shown in Figure 6.
Then proceed to splice the wires. Strip both wire ends about
1-1/2''. Be sure the surface is scraped clean. Overlap the two
ends so there is about 1/2” space between the insulation
ends. Twist the wire about 1-1/2 turns. With pliers, wind the
remaining wire on each end closely around the other wire as
shown. Use a soldering iron and a resin core solder or pure
solder with a non-acid soldering paste to solder the joint. 

After splicing, center the body of the insulator over the
splice. Slide the neoprene sleeves down into the recesses in
the body as far as they will go. Screw the caps on to the in-
sulator, tightening them securely by hand. This makes a
strong, waterproof splice.  

Method #2: Crimptype Connectors 

(Figure 6)

Stagger the pigtail ends of the motor leads and the cable. Cut
each lead about 4" longer than the last one. Trim the insula-
tion back 1/2" on each lead. Unscrew the plastic caps from
the insulator. Place parts on each end of the wire to be
spliced, as shown. 

Splice the wires with a butt-type connector using a crimp-
ing tool. After splicing, center the body of the insulator over
the splice. Slide the neoprene sleeves down into the re-
cesses in the body as far as they will go. Screw the caps onto
the insulator, tightening them securely by hand. This makes
a strong waterproof splice. 

7

Important Electrical Grounding Information

Hazardous voltage. Can shock, burn,
or kill. To reduce the risk of electri-

cal shock during pump operation, ground and bond the
pump and motor as follows:

A. To reduce risk of electrical shock from metal parts of the as-

sembly other than the pump, bond together all metal parts ac-
cessible at the well head (including metal discharge pipe, metal
well casing, and the like). Use a metal bonding conductor at
least as large as the power cable conductors running down the
well to the pump's motor. 

B. Clamp or weld (or both if necessary) this bonding conductor

to the grounding means provided with the pump, which will
be the equipment-grounding terminal, the grounding conduc-
tor on the pump housing, or an equipment-grounding lead.
The equipment-grounding lead, when provided, will be the
conductor having green insulation; it may also have one or
more yellow stripes.

C

. Ground the pump, motor, and any metallic conduit that car-

ries power cable conductors. Ground these back to the service
by connecting a copper conductor from the pump, motor, and
conduit to the grounding screw provided within the supply-
connection box wiring compartment. This conductor must be
at least as large as the circuit conductors supplying the pump.

Save these instructions.

End Caps

Gaskets

Wire Ends Ready to Splice:
Strip 1/2" back for crimp-type connectors
Strip 1-1/2" back for soldered connection

Wire Spliced (Crimped)

Insulator body 
centered 
over splice

Gasket sleeve 
in place

Cap screwed on

Wire Spliced (Soldered)

1182 0794

Figure 6: Crimped splice and soldered splice.

Содержание 390.284020

Страница 1: ...270 2 WIRE SUBMERSIBLE PUMP MODEL Nos 390 285510 390 285520 390 285530 CAUTION Read and Follow All Safety Rules and Operating Instructions Before First Use of This Product Save This Manual For Future...

Страница 2: ...relief valve Stock No 27220 6 With a new well test well water for purity before using Consult your local Health Department for procedure Hazardous voltage Can shock burn cause death or start fires 7...

Страница 3: ...4 7 9 390 284030 3 4 230 8 40 13 5 12 7 11 9 10 7 9 4 7 9 390 284040 1 230 10 40 13 5 12 9 11 9 10 9 9 8 7 4 390 284050 1 1 2 230 14 40 13 5 12 9 11 7 10 4 8 9 7 1 High Capacity Pumps with 1 1 4 Disch...

Страница 4: ...pe Well Seal Purchase Locally Conduit or Sleeve Cable Splices Plastic Pipe Adapter Plastic Pipe Adapter Pump Check Valve Torque Arrester Purchase Locally Centering Guide 1178 0794 Plastic pipe adapter...

Страница 5: ...e Air and Standard The Air Volume Control AVC maintains the cushion of air in Standard Tanks No Air Volume Control is needed with a Captive Air Tank Air Volume Control A device mounted on a standard t...

Страница 6: ...oltage and frequency of the electrical power supply If in doubt check with your electric power company or a licensed electrician Check Fusing and Wiring Chart before connecting wires from pressure swi...

Страница 7: ...lder with a non acid soldering paste to solder the joint After splicing center the body of the insulator over the splice Slide the neoprene sleeves down into the recesses in the body as far as they wi...

Страница 8: ...e distance to the water level in the well are not known See page 4 The pump should not be set closer than 5 feet from the bottom of the well and should be submerged 15 to 20 feet below the draw down w...

Страница 9: ...in installation draw ings Figure 1 Page 4 Using teflon tape on all male threads Assemble this unit to the plastic pipe in same manner as outlined in Step 6 Assembly may slip through well seal Install...

Страница 10: ...om of the well 6 Develop the well See Well Development and Pump Test below 7 Refer to Typical Pump Installation Drawings for proper method of piping depending on the type of pres sure tank used Well d...

Страница 11: ...ve to restrict flow until discharge rate does not exceed well recovery rate possibly seriously damaging pump To prevent possibility of dangerous high pressure install a relief valve in discharge pipe...

Страница 12: ...color coding of drop cable Pressure switch fails A Voltage too low motor will run slowly A Have a competent electrician verify voltage at electrical disconnect box 2 wire or to shut off pump causing l...

Страница 13: ...4270 Description 1 U17 1172 U17 1173 U17 1174 U17 1174 U17 1174 U17 1175 Start Capacitor 2 U17 1184 U17 1185 U17 1186 Solid State Switch 3 U17 1201 U17 1201 U17 1201 Terminal Strip 4 U17 1190 U17 1191...

Страница 14: ...U36 197SS U36 197SS U36 197SS Nut 5 16 Hex 4 Required 3 U43 115SS U43 115SS U43 115SS U43 115SS U43 115SS U43 115SS Lockwasher 5 16 4 Required 4 P3 510P P3 510P P3 510P P3 511P P3 512P P3 513P Lead Co...

Страница 15: ...U43 115SS Lockwasher 5 16 4 Required 4 P3 517P P3 518P P3 519P P3 546SS Lead Cover 5 U30 840SS U30 840SS U30 840SS U30 840SS Screw 8 32x5 16 4 Required 6 U30 927SS U30 927SS U30 927SS U30 927SS Screw...

Страница 16: ...250 390 284130 390 284260 390 284140 390 284270 2 WIRE SUBMERSIBLE PUMP MODEL Nos 390 285510 390 285520 390 285530 The model number of your Submersible Pump will be found on a plate attached to the pu...

Отзывы: