Seametrics EX100 Series Скачать руководство пользователя страница 15

EX100/200 SERIES INSTRUCTIONS

Seametrics • 253.872.0284 

Page 15 seametrics.com

Flow Rates 

(in gallons per minute)

OPERATION & MAINTENANCE

Filtering

The software of the EX100/200-Series filters out electrical 

noise and averages sudden variations in the flow to smooth 

the output. It takes a matter of seconds for the flow sensor 

to get up to full output when it is powered up or when flow 

begins.

Electrode Coating

Grease or other adhering, non-conductive materials can 

stop  flow  detection  if  the  electrodes  become  heavily 

coated. To clean the electrodes, remove the sensor from 

the pipe and gently scrub the electrodes (three silver 

bumps) on the reading face of the flow sensor. A mild soap 

(dishwashing liquid for example) can be used to aid the 

cleaning process.

Calibration (“K-Factor”)

In order to properly process pulses from the flow sensor, 

a number must be entered into the control to which the 

sensor is connected.  This number, called the K-factor, 

is the number of pulses the sensor puts out per unit of 

fluid  passing  through  the  pipe.    It  is  normally  provided 

for Seametrics sensors in pulses per gallon, and can be 

ascertained by using the “K-Factor Calculator” on the 

Seametrics website.  These numbers are based on extensive 

testing, which has shown close agreement among different 

EX sensors in the same installation. Typically, most K-factor 

error can be attributed to installation variables, such as 

depth setting and fitting configuration.

Zero Adjustment

When the EX100/200-Series meter is powered up and 

there is no flow, there should be no output pulses (or, if 

connected to the FT430/440, flow rate should read “0”).  If 

there  are  pulses,  it  may  be  necessary  to  adjust  the  flow 

meter under no-flow conditions after it has been installed. 

This should only be done if the indicated flow is low, 

near the lower cutoff.

Zero Adjustment

To perform the adjustment, after determining that there 

is  a  full  pipe  with  no  flow,  short  between  the  two  pins 

marked “Zero Adjust”. A red LED light will come on for 

approximately  50  seconds  and  then  go  out.    The  zero 

adjustment is completed.

Minimum Flow

As with any other flow sensor, there is a rate below which 

the EX100-Series sensor cannot read. Check the table 

below for the minimum flow rate detectable by the sensor 

for a given pipe size. 

Presence of Flow Indication.

  To assist in troubleshooting, 

the “Status LED” has two blinking modes in normal 

operation. When there is no flow detectable by the meter 

(below minimum threshold) the LED blinks every 8.0 

seconds. When there is detectable flow, the same indicator 

blinks every 3.0 seconds (Pulses are being output when 

indicator is blinking every 3 seconds).

  30Vdc

Max. 6mA

- +

- +

12-24Vdc

3

4

5

6

2

1

Power

Forward

Output

Status

LED

Zero

Adjust

Pins

Zero

Adjust

Pins

Status

LED

Using the K-Factor Calculator:

Go to 

seametrics.com

 and select the 

K-factor Calculator 

located at the bottom of the home page*.  

1.  Select your meter.  
2.  Choose units. 
3.  Input external pipe diameter (measure) and 

wall     thickness (measure, or look-up in Pipe Wall 

Thickness table on page 8 of this manual).

4.  Press Calculate to determine your K-factor.  

(

NOTE: 

Dimension D is also calculated.)

5.  Enter your K-factor into your controller.

    *For pipe sizes larger than 50”, please consult factory.

Feet 

Per 

Second

Nominal Pipe Size

3”

4”

6”

8”

10”

12”

14”

16”

18”

20”

24”

30”

36”

48”

Min 

0.28

6

11

25

44

69

99

134

175

222

274

395

617

888

1,580

Max 

20.0

440

783

1,762

3,133

4,895

7,050

9,596

12,533

15,863

19,584

28,200

44,064

63,452

112,804

Содержание EX100 Series

Страница 1: ...PROUDLY MADE IN THE USA C e rtified Compa n y ISO 9001 2008 EX100 200 Series Insertion Magnetic Flow Meter Instructions EX11x EX21x EX15x EX25x...

Страница 2: ...ections General Electrical Guidelines Page 11 Power Page 11 Output Page 11 Grounding Guidelines Page 11 Connection Diagrams Counter or PLC Page 12 A055 4 20 mA Output Page 12 FT520 Controller Page 12...

Страница 3: ...es converted using any of the Seametrics family of indicators and converters A modular system of electronics can be installed directly on the flow sensor or mounted remotely The FT430 externally power...

Страница 4: ...Valve Assembly 15x 25x only Bronze stainless optional with bronze ball valve Fitting Size Required 11x 21x 1 5 FNPT 15x 25x 2 FNPT Maximum Pressure 200 psi 14 bar Temperature Ambient 0 to 160 F 17 to...

Страница 5: ...are not recommended for installation downstream of a boiler feedwater pump where installation fault may expose the flow sensor to boiler pressure and temperature Maximum recommended temperature is 20...

Страница 6: ...ht If initial installation is performed on an unpressurized pipe cut a minimum 1 3 4 hole in the pipe If possible measure the wall thickness and write it down for use in depth setting Then install the...

Страница 7: ...ension D one more time 5 Fully tighten the compression nut Record your settings Once you have the meter set up and operational it is important to record you meter settings and save them future referen...

Страница 8: ...37 1 031 1 218 Stainless Steel 10S 0 120 0 120 0 134 0 148 0 165 0 180 0 188 0 188 0 188 0 218 0 250 0 312 0 312 Stainless Steel 40S 0 216 0 237 0 280 0 322 0 365 0 375 0 375 0 375 0 375 0 375 0 375 0...

Страница 9: ...age 9 seametrics com INSTALLATION Straight Pipe Recommendations X diameter 5X 10X Reduced Pipe Two Elbows In Plane Two Elbows Out Of Plane Expanded Pipe Swirling Flow Propeller Meter Partially Open Bu...

Страница 10: ...ault may expose the flow sensor to boiler pressure and temperature Maximum recommended temperature is 200 F Full Pipe Recommendations Better Installation Possible Problem Air can be trapped Allows air...

Страница 11: ...cable be sure to connect shield to ground at power supply end of the cable Do not connect other end of shield Avoid routing flow sensor cables in close proximity to a variable frequency drive Recomme...

Страница 12: ...dc Power Forward Output EX SERIES AO55 EX SERIES Sensor 4 20 mA 4 20 mA 24 Vdc Power 12V SEN1 G SEN2 EX SERIES 24 Vdc Power Power Forward Output FT520 Reverse Output Option 15 only Reverse Output Opti...

Страница 13: ...See Dual FT430 440 Diagram for an example of bidirectional connections _ _ _ _ _ _ _ S _ _ _ Power Pulse Out 2 Sensor Input Pulse Out 1 Scaled Scaled Reverse Output Option 15 only Power Forward Output...

Страница 14: ...ions Green White Black Red 12 24 Vdc Power _ S _ _ _ _ _ S _ _ _ Power Pulse Out 2 Sensor Input Pulse Out 1 Scaled 430 Pass Thru 440 Scaled 24 Vdc Power DL76 FT430 440 EX SERIES Sensor Input Reverse O...

Страница 15: ...es it may be necessary to adjust the flow meter under no flow conditions after it has been installed This should only be done if the indicated flow is low near the lower cutoff Zero Adjustment To perf...

Страница 16: ...h 100414 100414 7 Strain relief kit large includes 1 101850 101850 9 Tube Not field replaceable 10 Compression nut 100064 brass 100084 ss 11 Compression ferrule 100358 12 Adapter 100845 brass 100846 s...

Страница 17: ...ons Fluid conductivity 20 S cm Select another flow meter Output pulses incorrect Missing or incorrect ground wire Check for proper ground Incorrect depth setting Check depth setting see page 7 Fluid c...

Страница 18: ...Seametrics which cause damage to the products or cause abnormally frequent service calls or service problems h A new warranty period shall not be established for repaired or replaced material products...

Страница 19: ...EX100 200 SERIES INSTRUCTIONS Seametrics 253 872 0284 Page 19 seametrics com NOTES...

Страница 20: ...Seametrics 19026 72nd Avenue South Kent Washington 98032 USA P 253 872 0284 F 253 872 0285 1 800 975 8153 seametrics com LT 65200196r2 1 20161230 12 30 16...

Отзывы: