Savvio 15K SAS Product Manual, Rev. B
3
2.0
Applicable standards and reference documentation
The drive has been developed as a system peripheral to the highest standards of design and construction. The
drive depends on its host equipment to provide adequate power and environment for optimum performance
and compliance with applicable industry and governmental regulations. Special attention must be given in the
areas of safety, power distribution, shielding, audible noise control, and temperature regulation. In particular,
the drive must be securely mounted to guarantee the specified performance characteristics. Mounting by bot-
tom holes must meet the requirements of Section 8.3.
2.1
Standards
The Savvio family complies with Seagate standards as noted in the appropriate sections of this manual and the
Seagate SAS Interface Manual, part number 100293071.
The Savvio disc drive is a UL recognized component per UL1950, CSA certified to CAN/CSA C22.2 No. 950-
95, and VDE certified to VDE 0805 and EN60950.
2.1.1
Electromagnetic compatibility
The drive, as delivered, is designed for system integration and installation into a suitable enclosure prior to
use. The drive is supplied as a subassembly and is not subject to Subpart B of Part 15 of the FCC Rules and
Regulations nor the Radio Interference Regulations of the Canadian Department of Communications.
The design characteristics of the drive serve to minimize radiation when installed in an enclosure that provides
reasonable shielding. The drive is capable of meeting the Class B limits of the FCC Rules and Regulations of
the Canadian Department of Communications when properly packaged; however, it is the user’s responsibility
to assure that the drive meets the appropriate EMI requirements in their system. Shielded I/O cables may be
required if the enclosure does not provide adequate shielding. If the I/O cables are external to the enclosure,
shielded cables should be used, with the shields grounded to the enclosure and to the host controller.
2.1.1.1
Electromagnetic susceptibility
As a component assembly, the drive is not required to meet any susceptibility performance requirements. It is
the responsibility of those integrating the drive within their systems to perform those tests required and design
their system to ensure that equipment operating in the same system as the drive or external to the system
does not adversely affect the performance of the drive. See Tables 2 and 3, DC power requirements.
Содержание ST600MP0074
Страница 1: ...PRODUCT MANUAL Savvio 15K SAS 100407739 Rev B March 2007 ST973451SS ST936751SS ...
Страница 4: ...ii Savvio 15K SAS Product Manual Rev B ...
Страница 8: ......
Страница 10: ...2 Savvio 15K SAS Product Manual Rev B ...
Страница 14: ...6 Savvio 15K SAS Product Manual Rev B ...
Страница 30: ...22 Savvio 15K SAS Product Manual Rev B ...
Страница 34: ...26 Savvio 15K SAS Product Manual Rev B Figure 2 Typical ST936751SS current profile ...
Страница 50: ...42 Savvio 15K SAS Product Manual Rev B ...
Страница 78: ...70 Savvio 15K SAS Product Manual Rev B ...
Страница 85: ......