background image

d. Following the diagram in Figure 5, install the nut and lock washer on the cable and

insert the cable end through the panel and faceplate hole. Extend cable shaft out to
its fullest and install ferrule by screwing onto the cable shaft end. Do not over
tighten. Four or five turns are sufficient.

e. Place rubber o-ring seal onto the cable shaft and install the release handle by

screwing it onto the cable shaft. Do not tighten to the point where the pinhole in the
handle will be obstructed.

f. Push the handle into the ferrule. This will seat the o-ring seal. Align the pull pinholes

in the handle and ferrule and insert the pull pin (Figure 5).

g. Turn the handle so that the word FIRE is vertical. The handle can now be locked in

position by tightening the nut behind the face plate panel.

h. Temporarily remove pull pin and test cable operation. Cable must move freely

without friction or binding. Reinstall pull pin and confirm that release handle is now
locked in place.

i.

Attach the tamper resistant round plastic tie to the pull pin by passing tie through the
pull pin ring and around the cable assembly. Insert the end of the tie into cable end
and pull up snug. The tie provides a means of determining if manual discharge has
occurred.

j.

Nylon cable ties should be used for cable securing. Fasten and support the cable on
straight runs only. Do not secure at locations where cable forms a bend.

CAUTION: DO NOT USE NYLON CABLE TIES AS TAMPER FOR PULL PIN.

CAUTION: ACCIDENTAL DISCHARGE DURING HANDLING OR INSTALLATION MAY CAUSE

SERIOUS INJURY. DO NOT REMOVE FACTORY INSTALLED SAFETY PIN FROM
CYLINDER SENSOR VALVE/DETECTOR UNTIL INSTALLATION IS COMPLETED
AND CHECKED. WEAR EYE PROTECTION WHEN INSTALLING OR SERVICING
THE SYSTEM.

Step 3

Connecting cable assembly to cylinder (Figure 6 or 7)
a. 
Before attaching cable to the cylinder, check that the cylinder bracket is located

correctly and firmly mounted.

b. With the cylinder strapped in its bracket, pass the cable jacket ferrule completely

through the hole in the cylinder manifold. This will allow the necessary cable
flexibility needed for inserting the offset end of the flexible shaft into the actuator
lever. After connecting the shaft and actuator lever, move the cable back and align
the ferrule grove with the slot in the manifold. Insert the locking clip that is provided
with cable assembly. The cable assembly must be locked to the manifold or
accidental discharge can occur.

c. Using care, remove the factory installed actuator lever safely pin from the cylinder.

Store safety pin in the nylon retainer provided on the cylinder neck (Figure 6 or 7).

d. The Sea-Fire manual/automatic extinguisher is now fully operational.

8

AREA OF

MINIMUM

MAXIMUM

DIAMETER X

MODEL

PROTECTION

FM-200

®

FM-200

®

HEIGHT

MAN/

CU.FT.

CU.M.

AUTO

AUTO

RANGE

RANGE

LBS

KG

LBS

KG

IN

MM

FG25A

FG25M

0-25

0.0-0.7

-

-

1.0

0.5

2.5x9

64x229

FG50A

FG50M

26-50

0.7-1.4

1.0

0.5

2.2

1.0

3.1x12

79x305

FG75A

FG75M

51-75

1.4-2.1

2.2

1.0

3.3

1.5

3.1x15

79x381

FG100A

FG100M

76-100

2.1-2.8

3.3

1.5

4.4

2.0

3.5x15

89x381

FG125A

FG125M

101-125

2.8-3.5

4.4

2.0

5.4

2.4

4.1x16

104x406

FG150A

FQ150M

126-150

3.5-4.2

5.4

2.4

6.5

2.9

4.1x16

104x406

FG175A

FG175M

151-175

4.2-5.0

6.5

2.9

7.6

3.4

5.1x16

130x406

FG200A

FG200M

176-200

5.0-5.7

7.6

3.4

8.7

3.9

5.1x16

130x406

FG225A

FG225M

201-225

5.7-6.4

8.7

3.9

9.7

4.4

5.1x16

130x406

FG240A

FG240M

226-240

6.4-6.8

9.7

4.4

10.4

4.7

5.1x16

130x406

OPERATING TEMPERATURE RANGE:

0° TO 130T (-18° TO 54°C)

DISCHARGE TEMPERATURE:

FG-2S thru FG-75

212°F (100°C)

FG-100thruFG-240

165°F (74°C)

ALL FG MODELS APPROVED FOR VERTICAL OR HORIZONTAL MOUNTING.

Cubic Feet = CU.FT.

Kilograms = KG

Cubic Meters = CU.M.

 Inches= IN

Pounds = LBS

 Millimeters = MM

13

SPECIFICATION TABLE

SEA-FIRE “FG” SERIES AUTOMATIC FIRE EXTINGUISHERS

DOT 39/500 CYLINDER

Содержание FD1000A

Страница 1: ...FIRE EXTINGUISHERS INSTALLATION INSTRUCTIONS OWNER S MANUAL THIS MANUAL IS AN INTEGRAL PART OF THE SYSTEM AND AS SUCH THE EXTINGUISHER MUST BE INSTALLED AND MAINTAINED ACCORDINGLY U S COAST GUARD APPROVED FM APPROVED No 162 029 237 0 READ AND COMPLY WITH THESE INSTRUCTIONS WARNINGS AND LIMITATIONS BEFORE INSTALLING SUITABLE FOR USE FG MODELS 0 F 18 C TO 130 F 54 C FD MODELS 20 F 7 C TO 130 F 54 C ...

Страница 2: ... DISCLAIMER OF EXPRESSED AND IMPLIED WARRANTIES Metalcraft Sea Fire Marine Inc has taken reasonable care in preparing this document how ever since the use of this information and the conditions of use of the product are not within the control of Metalcraft Sea Fire Marine Inc it is the user s obligation to determine the con ditions of safe use of this product The information in this document is of...

Страница 3: ...nd or heart irregularities arrhythmias Misuse of the products by deliberately inhaling high concentrations of this gas could cause death without warning Persons with preexisting cardiac or central nervous sys tem disorders may be more susceptible to effects of an overexposure Section 12 Ecological Information No ecological information is available Section 13 Disposal Considerations Dispose of wast...

Страница 4: ...t the combustion reaction cannot sustain itself CAUTION IN CASE OF EXTINGUISHER DISCHARGE DO NOT RUSH TO OPEN THE PROTECTED COMPARTMENT LET THE EXTINGUISHING AGENT WORK FOR SEVERAL MINUTES HAVE A PORTABLE EXTINGUISHER AVAILABLEAND USE CARE WHEN OPENING THE COMPARTMENT AVOID BREATHING FIRE RELATED FUMES OR VAPOR NOTE It is important to retain the designed vapor concentration within the compartment ...

Страница 5: ... 2 0 AMPS AT 28 VDC For applications requiring larger load capacities see optional equipment section in this manual or contact factory ENGINES AND POWERED VENTILATION BLOWERS DIESEL ENGINES Continued operation of diesel engine s and or powered ventilation units will deplete the extinguishing agent and may cause a fire re flash Diesel engine s must be automatically shutdown upon extinguisher discha...

Страница 6: ...26 150 3 5 4 2 5 4 2 4 6 5 2 9 5 2x17 0 132x476 FD175A FD175M 151 175 4 2 5 0 6 5 2 9 7 6 3 4 5 2x17 0 132x476 FD200A FD200M 176 200 5 0 5 7 7 6 3 4 8 7 3 9 5 2x17 0 132x476 FD225A FD225M 201 225 5 7 6 4 8 7 3 9 9 7 4 4 5 2x17 0 132x476 FD250A FD250M 226 250 6 4 7 1 9 7 4 4 10 8 4 9 6 9x18 0 175x463 FD275A FD275M 251 275 7 1 7 8 10 8 4 9 11 9 5 4 6 9x18 0 175x463 FD300A FD300M 276 300 7 8 8 5 11 9...

Страница 7: ...0 APPROVED FOR VERTICAL OR HORIZONTAL MOUNTING MODEL FD 1050 thru FD 1500 FOR VERTICAL MOUNTING ONLY Cubic Feet CU FT Kilograms KG Cubic Meters CU M Inches IN Pounds LBS Millimeters MM V M E O R U O T N N I T L C I Y A N L G 14 Step 5 Locate bracket in desired position Vertical Sensor Valve Detector Head Up or Horizontal Figure 2 Using the bracket as a template mark and drill holes in bulkhead and...

Страница 8: ...6 or 7 a Before attaching cable to the cylinder check that the cylinder bracket is located correctly and firmly mounted b With the cylinder strapped in its bracket pass the cable jacket ferrule completely through the hole in the cylinder manifold This will allow the necessary cable flexibility needed for inserting the offset end of the flexible shaft into the actuator lever After connecting the sh...

Страница 9: ...l and making to determine the applicable DOT specification The discharged extinguisher may be refilled upon the prepaid return of the discharged system Contact factory or authorized dealer for detail RETURN TO UNITED STATES SEA FIRE MARINE Division of Metalcraft Inc 9331 A Philadelphia Road Baltimore Maryland 21237 USA EUROPE SEA FIRE EUROPE LTD Unit 7 io Centre Stephenson Road Fareham Hampshire P...

Страница 10: ...icate the ability to discharge the agent but not the quantity of extinguishing agent The cylinder less bracket must be weighed on at least a semiannual basis and be replaced immediately if gross weight has decreased by quantity noted on the specification label Never paint or obstruct the cylinder manifold or sensor valve detector as this will adversely affect its operating characteristic FD models...

Отзывы: