2012.03 / e
LEROY-SOMER
Installation and maintenance
R 450
AVRs
4531 en -
3 - TECHNICAL CHARACTERISTICS
3.1 - Electrical characteristics
- maximum power supply: 150V - 50/60 Hz
- Rated overload current: 10 A - 10 s
- Electronic protection:
- In the case of a short-circuit, the excitation
current is reduced to a value less than 1A
after 10 s
- In the event of loss of voltage reference,
the excitation current is reduced to a value
less than 1A after 1s for AREP/SHUNT, 10 s
for PMG.
- In the event of overexcitation, the current
is reduced as indicated in the next diagram
(see 3.2.1.4).
- Fuses: F1 on X1 and F2 on Z2 10A, 250V.
- Voltage sensing
• 0-110 V terminals = 95 to 140 V
• 0-220 V terminals = 170 to 260 V
• 0-380 V terminals = 340 to 528 V
For other voltages, a transformer should be
used.
- Voltage regulation:± 0.5%.
- Current sensing: (parallel operation): input
S1, S2 intended for 1 C.T. < 2.5 VA cl1,
secondary 1 A or 5 A.
3.2 - Configurations:
3.2.1 - Settings
3.2.1.1 - Voltage
Voltage adjustment via potentiometer
P1
in
the ranges described in the table below:
For 50 and 60 Hz
Max.
High range
320V < Un ≤ 530 V
Low range
80 V ≤ Un ≤ 320 V
WARNING
The allowed adjustment range is
±
5%;
when the setting exceeds these limits,
please check that it is conform with the
power table.
3.2.1.2 - Quadrature droop:
Quadrature
droop
adjustment
via
potentiometer
P4
within a range :
- from 0 to 8% with a PF=0.8 for 400V
applications.
- From 0 to 14% with a PF=0.8 for 240V
applications.
- From 0 to 8% for 110V applications with a
step-up transformer (ratio of 4) placed on
the voltage reference.
The potentiometer
P4
has a non linear
response. Then, when a 1A secondary CT is
connected the effective range starts from
the the second 1/3 of
P4
range and in the
case of a 5A secondary CT the effective
range starts from the first 1/3.
When a 5A CT is used, the adjustment range
is higher, so
P4
must be set to the first 1/4
(anti-clockwise) and then progressively
increase it.
WARNING
The CT must be connected.
3.2.1.3 - Stability:
Stability adjustment via potentiometer
P2.
Selection of rotating switch according to the
machine type and the response time as
indicated in paragraph 3.2.3.
3.2.1.4 - Excitation limitation:
Excitation limitation adjustment via
potentiometer
P3
as described below.
The excitation current limitation threshold in
steady state is set by a potentiometer at
110% of the rated value. The adjustment is
made by the operator during the on-load test
at rated power by tuning the potentiometer.
When the excitation current exceeds this
value, a counter is activated at the speed of
one record per second for 90 s. When this
time is elapsed, the current is reduced to the
value of the rated excitation current. If in the
meantime the excitation current drops
below the threshold value, the counter
counts down at the same speed.
256/285
Содержание R 340 U
Страница 1: ...User and maintenance manual for generating sets R340U 33504081101NE_0_1 ...
Страница 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 285 ...
Страница 18: ...Sockets voltage 208 120V 16 285 ...
Страница 32: ...Figure 4 3 Braking transmission Figure 4 4 Cross bar fitting Figure 4 5 Tandem bearing fitting 30 285 ...
Страница 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 285 ...
Страница 126: ...124 285 ...
Страница 128: ...126 285 ...
Страница 129: ...127 285 ...
Страница 130: ...128 285 ...
Страница 131: ...129 285 ...
Страница 132: ...130 285 ...
Страница 133: ...131 285 ...
Страница 134: ...132 285 ...
Страница 135: ...133 285 ...
Страница 136: ...134 285 ...
Страница 137: ...135 285 ...
Страница 138: ...136 285 ...
Страница 139: ...137 285 ...
Страница 140: ...138 285 ...
Страница 141: ...139 285 ...
Страница 142: ...140 285 ...
Страница 143: ...141 285 ...
Страница 144: ...142 285 ...
Страница 145: ...143 285 ...
Страница 146: ...144 285 ...
Страница 147: ...145 285 ...
Страница 148: ...146 285 ...
Страница 149: ...147 285 ...
Страница 150: ...148 285 ...
Страница 151: ...149 285 ...
Страница 152: ...150 285 ...
Страница 153: ...151 285 ...
Страница 154: ...152 285 ...
Страница 155: ...153 285 ...
Страница 156: ...154 285 ...
Страница 157: ...155 285 ...
Страница 158: ...156 285 ...
Страница 159: ...157 285 ...
Страница 160: ...158 285 ...
Страница 161: ...159 285 ...
Страница 162: ...160 285 ...
Страница 163: ...161 285 ...
Страница 164: ...162 285 ...
Страница 165: ...163 285 ...
Страница 166: ...164 285 ...
Страница 167: ...165 285 ...
Страница 168: ...166 285 ...
Страница 169: ...167 285 ...
Страница 170: ...168 285 ...
Страница 171: ...169 285 ...
Страница 172: ...170 285 ...
Страница 173: ...171 285 ...
Страница 174: ...172 285 ...
Страница 175: ...173 285 ...
Страница 176: ...174 285 ...
Страница 177: ...175 285 ...
Страница 178: ...176 285 ...
Страница 179: ...177 285 ...
Страница 180: ...178 285 ...
Страница 181: ...179 285 ...
Страница 182: ...180 285 ...
Страница 183: ...181 285 ...
Страница 184: ...182 285 ...
Страница 185: ...183 285 ...
Страница 186: ...184 285 ...
Страница 187: ...185 285 ...
Страница 188: ...186 285 ...
Страница 189: ...187 285 ...
Страница 190: ...188 285 ...
Страница 191: ...189 285 ...
Страница 192: ...190 285 ...
Страница 193: ...191 285 ...
Страница 194: ...192 285 ...
Страница 195: ...193 285 ...
Страница 196: ...194 285 ...
Страница 197: ...195 285 ...
Страница 198: ...196 285 ...
Страница 199: ...197 285 ...
Страница 200: ...198 285 ...
Страница 201: ...199 285 ...
Страница 202: ...200 285 ...
Страница 203: ...201 285 ...
Страница 204: ...202 285 ...
Страница 205: ...203 285 ...
Страница 206: ...204 285 ...
Страница 207: ...205 285 ...
Страница 208: ...206 285 ...
Страница 209: ...207 285 ...
Страница 210: ...208 285 ...
Страница 211: ...9 2 Appendix B Alternator user and maintenance manual 209 285 ...
Страница 212: ...210 285 ...
Страница 214: ...212 285 ...
Страница 237: ...23 LEROY SOMER 2011 01 h Installation and maintenance LSA 46 2 4 POLES ALTERNATORS 3856 en 235 285 ...
Страница 238: ...LEROY SOMER16015ANGOULÊMECEDEX FRANCE 338 567 258 RCS ANGOULÊME www leroy somer com 236 285 ...
Страница 249: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 247 285 ...
Страница 269: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 267 285 ...
Страница 270: ...www leroy somer com 268 285 ...