The 931 EntryCheck

 accepts 12 to 24 volts AC/DC.  System current draw (maximum):

                           Standby: 10mA at 12 volts, 25mA at 24 volts
                           During Operation: 250mA max (with illuminated Keypad)

IMPORTANT: 

The maximum output current allowed is 1 Amp. Check the specifications of your locking device. 

Make sure that the locking device and the 931 (250mA) combined draw less than 1 Amp. For locking devices that 
draw more current, a separate power supply is required. (See Appendix B pg 14)

Note:

If connecting DC, make the connections to “DC IN/OUT” instead of “12-24V AC/DC IN” (see Circuit Board 

Layout pg 13). Make sure the polarity is correct. 

INPUT REQUIREMENTS

OUTPUT CAPABILITIES

The 931 EntryCheck

 provides two SPDT dry contact relays (rated at 6 Amps at 120 VAC). Each relay can be 

configured to perform one of many different functions depending on the specific access control requirement. 
User Authorization to control each relay is determined by Setting Relay Options (see System Hardware Setup           
pg 8). Each relay can be configured for one of the following options:

1.  Voltage Output – Fail Safe or Fail Secure Locking Device

2.  Dry Contact Output – Control a Gate Operator/Garage Door

3.  CCTV OR Light Controller – First key press triggers a 10 second output

4.  Doorbell – Press     at the keypad to trigger a 1 second output for a doorbell 

(not included). This function is only available with a 12 Pad 3x4 or Thinline 2x6.

5.  Auxiliary Output – Momentary or Manual Control of an electronic device.

OPERATING TEMPATURES

Operating temperatures can range from -40°C to +70°C (-40°F to 160°F).  The 931 is compatible with any of the 
following Keypad styles/configurations:

KP-4U

KP-3Y

KP-3U

KP-2U

P:\INSTALLATION INST\Access Control\INST-931.vsd     0505     Page 4

*

Содержание EntryCheck 931-KP-2U

Страница 1: ...ryCheck The 931 EntryCheck is an easy to program easy to use stand alone self contained system with features suitable for basic access control requirements Providing either a voltage output or dry con...

Страница 2: ...NG THE LOCKING DEVICE 7 BATTERY BACK UP 7 SYSTEM HARDWARE SETUP 8 REMOTE BY PASS 8 ANTI TAILGATING 8 SETTING RELAY OPTIONS 8 9 TAMPER ALARM LOCKOUT 9 SYSTEM PROGRAMMING 10 OVERVIEW OF SYSTEM CODE PROG...

Страница 3: ...Length 6 Codes 1 Master 5 User of User Codes 1 3 5 7 9 Default Master Code 25 Incorrect Key Presses Tamper Alarm Non Volatile Memory Access Code Protection 40 C to 70 C 40 F to 160 F 100 Relative Humi...

Страница 4: ...e configured to perform one of many different functions depending on the specific access control requirement User Authorization to control each relay is determined by Setting Relay Options see System...

Страница 5: ...ble may be spliced The maximum distance between the Keypad and the Control Module must not exceed 1 000 feet For runs over 200 feet 18 gauge wire should be used Under 200 feet 20 gauge is acceptable 4...

Страница 6: ...25mm drill bit 3 Place the connector on the back of the keypad in the large hole Mark the keypad mounting holes 4 Drill clearance holes in accordance with fastening method used If mounting to wood dri...

Страница 7: ...ch system are two MOV s metal oxide varistor The function of the MOV is to absorb any inductive kickback from the locking device protecting the circuit board The MOV s have been installed under the re...

Страница 8: ...p the MONITOR screw terminals with factory installed wire SETTING RELAY OPTIONS The 931 provides a variety of options for configuring both relays These options include User Unlock Authorization Latchi...

Страница 9: ...Authorization relay for that particular User Group will energize and remain energized until a valid code followed by 7 is entered again Ex Latching Authorization P INSTALLATION INST Access Control INS...

Страница 10: ...9 However the Master Code cannot be configured to Latch either relay PROGRAMMING THE MASTER CODE To Program Change the Master Code 1 Select a 3 to 8 digit code that will be used for the Master Code _...

Страница 11: ...for every one second increment and 5 s for every five second increment that equal your desired Door Open Time Each valid key press a 1 or a 5 will generate a double beep Do not let more than five sec...

Страница 12: ...and you will have to start over For an existing Installation There are typically two reasons for code loss static or inductive kickback There is no way to determine if the system has been affected by...

Страница 13: ...APPENDIX A CIRCUIT BOARD LAYOUT P INSTALLATION INST Access Control INST 931 vsd 0505 Page 13...

Страница 14: ...r relay to eliminate chatter Fail Secure Lock Fail Safe Lock Controlled by KE 265 Controlled by KE 265 CCTV DOORBELL and Fail Secure Lock Garage Door Gate Drive Controlled by KE 265 Controlled by KE 2...

Страница 15: ..._________ Master Code 2 User Name__________________________ Master Code 3 User Name__________________________ Master Code 4 User Name__________________________ Master Code 5 P INSTALLATION INST Access...

Отзывы: