Configure Sense Input  

Default:  INHIBIT

The Sense Input (gray wire) can be programmed for either 
DOOR SENSE or INHIBIT.

Press:  10 # Input #

Input=0 for Door Sense; =1 for Inhibit

When programmed for DOOR SENSE, if an open condition on 
the input occurs before access is granted (with an entry code or 
with the request-to-enter input) a FORCED ENTRY output will 
occur.  If an open condition remains 60 seconds after a relay 
activation for access, a DOOR AJAR output will occur.  

When programmed for INHIBIT, a closed condition on the input 
will prevent Relay #1 from activating when access is requested 
with an entry code.  This mode is typically used with an external 
timer to disable the access device at certain times.

Select Forced Entry Output

Default:  No Output

Sets which output activates if the DOOR SENSE input opens 
before access is granted.  This output is timed and configured 
by the relay “On-time”.

Press:  11 # Output #

Output=Output to Activate(0-4)

1=Main Relay;  2=Auxiliary Relay;  3=Output #3;  4=Output #4;  

0=No Output

Select Door Ajar Output

Default:  No Output

Sets which output activates if the DOOR SENSE input stays 
open 60 seconds after access is granted (door ajar time is 
adjustable using Function 25).  This output is not timed.

Press:  12 # Output #

Output=Output to Activate (0-4)

1=Main Relay;  2=Auxiliary Relay;  3=Output #3;  4=Output #4;  

0=No Output

Select Keypad Active Output

Default:  No Output

Sets which output activates when any keys are pressed.  This 
output is timed.  If toggle mode is selected for the output, the timer 
value defaults to 2 seconds.

Press: 14 # 

Output

#  

Output=Output to Activate(0-4)

1=Main Relay;  2=Auxiliary Relay;  3=Output #3;  4=Output #4; 

0=No Output

Select Keypad Lockout Output

Default:  No Output

Sets which output activates when the keypad is “locked out” after 
too many incorrect entry code attempts. The lockout time is 60 
seconds.

Press: 13 # 

Output

#  

Output=Output to Activate (0-4)

1=Main Relay;  2 = Auxiliary Relay;  3=Output #3; 4=Output #4;  

0=No Output

Select Alarm Shunt Output

Default:  No Output

Sets which output activates during the time access is granted.  
(Use this output ot shunt alarm contacts attached to the access 
door.)  This output may be timed or toggled.

Press: 15 # 

Output

#  

Output=Output to Activate(0-4)

1=Main Relay;  2=Auxiliary Relay;  3=Output #3;  4=Output #4; 

0=No Output

Select Request-to-Exit Output

Default:  No Output

Sets which output activates when the Request-to-Exit input is 
grounded.  This output may be timed or toggled.

Press: 16 # 

Output

#  

Output=Output to Activate(0-4)

1=Main Relay;  2=Auxiliary Relay;  3=Output #3;  4=Output #4; 

0=No Output

REX input terminates toggle of Main or Aux. Relay

Main Relay On-time

Default:  02 Seconds

Sets the length of time the Main Relay activates when triggered.

Green LED is on when Main Relay is active.

Press: 21 # 

Seconds

#  

Seconds=Output time in seconds (1-60)

Auxiliary Relay On-time

Default:  02 Seconds

Sets the length of time the Auxiliary Relay activates when triggered.

Press: 22 # 

Seconds

#  

Seconds=Output time in seconds (1-60)

P:\INSTALLATION INST\Access Controls\INST-926\INST-926.vsd     Rev -

01-18     Page 5

Anti-Tamper Output

Default:  No Output

Sets which output activates when the Anti Tamper switch on the 
back of the keypad is activated. 

Press: 17 # 

Output

#  

Output=Output to Activate(0-4)

0=No Output;  2=Auxiliary Relay;  3=Output #3;  4=Output #4;  

Changing the 6-Digit Master Programming Code

Press: 98 # 

Master Code

Master Code

#  

Master Code=The new 6-digit Master Programming Code

Erasing All Entry Codes

WARNING:  PERFORMING THIS COMMAND WILL REMOVE 

ALL ENTRY CODES FROM THE MEMORY

Press: 97 # 0 0 0 0 0 0 #  0 0 0 0 0 0 #  

Note: 

The green indicator will light while the memory is being erased.  This 

may take up to 15 seconds.

Содержание 926 EntryCheck

Страница 1: ...ormally open pushbutton or wireless switch to provide codeless activation of the Main Relay Auxiliary Relay Output 3 or Output 4 user programmable The ALARM SHUNT signal is available when access is granted This signal can be programmed to activate any of the relays or solid state outputs to shunt alarm contacts on the access door gate preventing the triggering of an alarm when an authorized access...

Страница 2: ...s Program the first user code Step 1 Enter 9 123456 Enter the program mode default master code Step 2 Enter 03 4 Set the entry code length to 4 digits Step 3 Enter 21 5 Set the main relay activate time to 5 sec Step 4 Enter 01 001 9876 9876 1 PIN code 9876 is assigned to User 001 to momentarily activate the main relay Step 5 Enter Exit programming mode Adding additional user codes Once the code le...

Страница 3: ...ring TO POWER SUPPLY KEYPAD POWER 12 or 24 VOLTS AC OR DC RED BLACK AUXILIARY RELAY 2 AMPS 28VDC MAX NC NO COM ORG BLK BLK WHT BRN YEL FAIL SECURE CONNECTION FAIL SAFE CONNECTION MAIN RELAY 5 AMPS 28VDC MAX NC COM NO ORANGE WHITE YELLOW BLACK PINK SALMON GREEN GRAY BLACK VIOLET BLACK BLUE DOOR POSITION SWITCH N C REQUEST TO EXIT SWITCH N O COMMON OUTPUT 4 OUTPUT 3 NOT USED COMMON SENSE REQUEST TO ...

Страница 4: ...ory The green indicator will light when the new code is accepted If the user number already exists or an entry error has been made the red indicator will light Delete the user and re enter the new information again Note Leading zeros zeros before the code number i e 0001 do not need to be entered when programming a new code The 926 will internally add any zeros to fill digits determined by the ent...

Страница 5: ...activates when the keypad is locked out after too many incorrect entry code attempts The lockout time is 60 seconds Press 13 Output Output Output to Activate 0 4 1 Main Relay 2 Auxiliary Relay 3 Output 3 4 Output 4 0 No Output Select Alarm Shunt Output Default No Output Sets which output activates during the time access is granted Use this output ot shunt alarm contacts attached to the access door...

Страница 6: ... During Main Relay Default No Selects whether or not the keypad beeps during Main Relay activation Press 41 Sound Sound 1 for Yes 0 for No Solid state Output 4 On time Default 02 Seconds Sets the length of time Output 4 activates when triggered Press 24 Seconds Seconds Output time in seconds 1 60 99 Toggle Mode Beep Sounds on Keystrokes Default Yes Selects whether or not the keypad beeps as each k...

Страница 7: ... Use supplied hardware or other appropriate hardware suitable for your specific mounting surface Clean any debris out of the enclosure that may cause a short If the keypad is used to activate a gate operator mount the keypad a minimum of 6 from the gate and gate operator to avoid contact with the movement of the gate upon activation POST MOUNT SURFACE MOUNT 1 DIA 4X 3 8 DIA 2 7 8 2 7 8 ...

Отзывы: