background image

REFRIGERATION SERVICE

General:

••

Scotsman recommends that any work on the
refrigeration system only be done when it is
certain that the system needs repair. 

••

Refrigerant should not be added except as a
way to determine the proper operation of the
product. If the system was low on refrigerant,
there is a leak, and it must be found and
repaired.

••

Although this system uses R-22, it should not
be wasted to the atmosphere, but reclaimed.

••

This system has a critical charge, it must be
recharged with the correct amount of refrigerant
as listed on the nameplate of the ice machine,
or performance will suffer.

••

Anytime the refrigeration system has been
opened, the dryer should be replaced.

••

When brazing the tubing connections to the hot
gas valve or thermostatic expansion valve, the
component must be protected by heat sink
material.

Specifically:

Recover, reclaim or recycle refrigerant. The
method chosen is up to the service company.
There are various mechanical devices that may be
used to recycle refrigerant at the field level,
however, Scotsman requires that any refrigerant
placed into a Scotsman ice machine meet ARI
spec 700. Reclaim programs are available thru
most refrigerant wholesalers. 

Use conservation minded service procedures: 

••

Refrain from checking refrigeration pressures
without reason. There are many ways to
determine the proper operation of a Scotsman
ice machine without using refrigerant gauges.
Visual inspection of the water system,
observation of the ice formation, amp draw,
voltage, and other techniques will lead to proper
diagnosis. Scotsman also recommends that, at
the time of initial start up, gauges not be used.

••

If gauges must be used, do not always check
the high side pressure. If the condenser is clean
and seems to be operating correctly, it most
likely is. The low side pressure is much more
important on an ice machine than is the high
side. 

••

If gauges must be used, use very short hoses.
Minimal refrigerant discharged into the hoses

equals minimal refrigerant discharged into the
air. 

••

If hi side pressure must be checked, use a
quick connect at the end of the discharge hose
to minimize the release of refrigerant, J/B
Industires part number A33000 works well. 

••

Scotsman’s schrader valve caps must be
tightened to 70 inch - pounds to insure that the
valves will not leak. 

••

If using recycled refrigerant, it must meet ARI
spec 700 or have been cleaned by a machine
capable of attaining ARI spec 700. 

If the refrigeration system must be serviced, the
quality of service must insure that there will not be
a repeat failure, as repeat failures will cause
refrigerant to be discharged into the air by the
failure or when the failure is corrected:

••

If there has been a compressor burn out, check
for acid in the oil. If acid is indicated, extra steps
must be taken to clean up the system. 

••

Never use refrigerant, such as R-11, to clean
up or flush out a refrigeration system. When
system clean-up is required, the use of suction
line filter-dryers and liquid line filter-dryers are
recommended.

••

Always replace the dryer when repairing a leak
or replacing a refrigeration component. 

••

Evacuate the system with a good vacuum
pump to 500 microns or less. If the triple
evacuation method is used, the vacuum should
be broken each time with dry nitrogen, not
refrigerant. Evacuation must be from both sides
of the system. 

••

Weigh in or measure in the nameplate charge.
Recharge into the high side.

••

Check for leaks with a high quality, electronic
leak detector. Halide torches will not locate the
very small leaks. 

••

Scotsman’s schrader valve caps must be
tightened to 70 inch - pounds to insure that the
valves will not leak. 

If an ice machine is to be discarded and still
contains refrigerant, Scotsman recommends that
the refrigerant be recovered, reclaimed, or
recycled so that it is not discharged into the air.

MCM1462

April, 1993

Page 25

Содержание MCM1462

Страница 1: ...staller Location Assembly 3 Stacking 4 For the Electrician 5 For the Plumber 6 Final Check List 7 Initial Start Up 8 Freeze Cycle Operation 10 Harvest Cycle Operation 11 Component Description 12 Clean...

Страница 2: ...he MCM1462 will fit the MDB900 ice storage bin 48 wide It will double stack with kit KSMCM48 The stacking kit includes Relay box and wires to interconnect bin controls Stainless steel panel bracket to...

Страница 3: ...e the machine Do NOT push the bin into postion instead lift it there Pushing a bin may damage the legs and leg mounts Level the bin in both the front to rear and side to side directions by adjusting t...

Страница 4: ...ker The top removed from the lower icemaker will no longer have any function A stainless steel bracket from the kit must be attached to the top of the bottom machine before the units are stacked Place...

Страница 5: ...itions Low voltages can cause erratic operation and may be responsible for serious damage to the icemaker Electrical connections are made at the rear of the icemaker inside the junction box All extern...

Страница 6: ...r foot on horizontal runs The drains to be installed to conform with the local plumbing code Install a vertical open vent on drain line high point to insure good draining The ideal drain receptacle is...

Страница 7: ...tor plates 7 Have all electrical water and drain connections been made 8 Is the water supply line shut off valve installed and electrical wiring properly connected 9 Check all refrigerant lines and co...

Страница 8: ...ll close the water inlet solenoid valve and the water fill cycle is complete If the sump is not full rotate the timer once again to repeat the harvest cycle The water pump should be pumping water thro...

Страница 9: ...the icemaker in the harvest cycle place something directly below the transducer socket The machine should switch off at the END OF THE HARVEST CYCLE Within seconds after removal of the obstruction th...

Страница 10: ...CLOSED When the ice cubes are partially formed the cube size control sensing bulb attached to the suction line will CLOSE and connect power to the timer motor The timer then controls the remainder of...

Страница 11: ...te by the warming effect of the hot gas condensing in each evaporator plate and the water cascading over the ice cubes The released ice cubes drop into the ice storage bin below At the end of the harv...

Страница 12: ...ch harvest cycle and prevents short cycling on the bin thermostat control Timer Timer Switch Assembly The timer cam is controlled by the cube size control The outer surface or large diameter lobe of t...

Страница 13: ...When set at FULL it will not allow the machine to fill the bin any closer to the ice machine than about 8 and it will not work if the distance to the bottom of the bin is greater than 8 feet Because i...

Страница 14: ...ates Gravity flow returns the unfrozen excess portion of water to the sump reservoir for recirculation Hot Gas Solenoid Valve The hot gas solenoid valve opens only during the harvest cycle to divert t...

Страница 15: ...the reservoir drain cap and drain the cleaning solution from the sump Replace the drain cap 12 Rotate the shaft of the timer and switch assembly CLOCKWISE to the harvest position low part of the cam a...

Страница 16: ...After all the scale has been removed rinse all of the surfaces inside the bin with clean potable water To sanitize the bin and ice machine interior Use an approved sanitizer and follow the directions...

Страница 17: ...rect ice cube size is achieved To produce SMALLER sized ice cubes 1 Locate the cube size control on the front of the control box 2 Rotate the adjusting knob one eighth of a turn COUNTER Clockwise 3 Ob...

Страница 18: ...e cube size control Rotating the shaft of the timer cam clockwise will allow putting the machine into either the freezing cycle or harvest cycle as required in the cleaning instructions To Adjust The...

Страница 19: ...of the ice machine 1 2 22 from the base of the ice machine 1 4 30 from the base of the ice machine CHARACTERISTICS This machine uses R22 AIR COOLED Freeze cycle Average Discharge Pressure at 900 700...

Страница 20: ...intake temperature too high air cooled Reduce room temperature Sump covers out of position Re position sump covers Cubes too small Adjust cube size Cube size control stuck open Replace cube size contr...

Страница 21: ...tem Purge system evacuate and weigh in nameplate charge Poor air circulation or extreme hot location Relocate the cabinet or provide ventilation Overcharge of refrigerant Evacuate and weigh in namepla...

Страница 22: ...circuit by attaching a jumper wire between bin thermostat posts on circuit board part no 12 1912 01 the circuit board with the timer on it Reconnect power If machine does not start go back to machine...

Страница 23: ...attachment for the left water distributor tube and notch also that the distributor manifold connections at the top center of each evaporator plate is snug against the top of the plate Cube Size Contr...

Страница 24: ...F water supply to machine 2 Loosen and remove outlet water line from the inlet water solenoid valve assembly 3 Remove screws and pull the water solenoid valve out to gain access 4 Pull electrical cord...

Страница 25: ...important on an ice machine than is the high side If gauges must be used use very short hoses Minimal refrigerant discharged into the hoses equals minimal refrigerant discharged into the air If hi sid...

Отзывы: