CS55 SERVICE DIAGNOSIS
SYPMTOM............................... POSSIBLE CAUSE
SUGGESTED CORRECTION
Unit will not run........................ Blown fuse or
Replace fuse & check for
............................................ breaker
cause of blown fuse, reset breaker.
Compressor cycles .................. Low voltage
Check circuit for
intermittently ............................
overloading. Check voltage at the
............................................
supply to the building.
............................................ Dirty condenser
Clean the condenser
............................................ Air circulation
Allow sufficient air
............................................ blocked
around unit.
............................................ Non condensable
Evacuate and recharge
............................................ gas in system
with nameplate charge
Cubes too small....................... Cube size control
Check and adjust for
............................................ set too warm
proper operation
............................................ Partially restricted
Blow charge, evacuate
............................................ cap tube
with new drier, weigh in nameplate charge.
............................................ Moisture in system
Same as above
............................................ Overcharged
Same as above
............................................ Undercharged
Same as above, look for a leak.
Cloudy cubes........................... Spray nozzels
Clean
............................................ plugged
............................................ Needs cleaning
Clean with Scotsman Ice Machine Cleaner
Irregular size............................ Some jets plugged
Clean jets
cubes, some cloudy .............. Shortage of water
Check water supply
Cubes too large ....................... Cube size control
Check and adjust for
set improperly..................... proper operation
Decreased ice ......................... Inefficient
Replace
capacity.................................... compressor
December 1987
Page 13