Condensing Section Assembly
Alternate Assembly:
The CP unit may be connected to an approved
condenser coil in a central condenser rack. In
those cases, the CP unit must be connected to the
condenser coil using special kit RTE10.
Position the CP unit in its final spot. It must be
within 6 feet of the condenser coil connections.
Route tubing from kit RTE10 from the CP unit to
the condenser coil.
Connect tubing per the Coupling Instructions in this
manual.
No wire connection is required between the CP
unit at the condenser.
Note: Approved condensers must maintain power
to their fan motor at all times.
All Assemblies:
Route interconnecting control wire through proper
hole in side of CP unit and plug into the connection
on the bottom of the control box.
Route power conduit (liquid tight) and wires to the
hole in the side of the CP unit. Secure with the
proper type of connector.
Note: The power supply wires must be the correct
size and type per the National Electric Code.
Locate the nameplate on the CP unit for the
Voltage, Phase, Minimum Circuit Ampacity and
Maximum Fuse Size. Either fuses or HACR type
circuit breakers may be used.
Follow all Local, State and National Codes.
Connect power wires to the contactor, L1 and L2 if
single phase, L1, L2 and L3 if three phase. Note: If
there is a “wild leg” in the three phase power
supply place it on L3.
Connect electrical power to the CP unit.
Return front of CP unit to its original position.
Eclipse
ä
2000
September 2003
Page 17
Control Wire Connection in CP Unit
Interconnecting
Control Wire Plug
CP Unit Contactor, Three Phase Shown
Connect
Power
Here
Connect
Fan Motor
Leads
Approved
Central
Condenser
Unit
Scotsman
Condensing
Unit