Installation: Product Specifications
Location Limitations
This ice system is made up of three parts, the ice
making machine, or head; the remote condenser;
and the interconnecting tubing. The ice making
machine must be installed indoors, in a controlled
environment. Space must be provided near the
machine for service access. The remote condenser
may be installed above or below the ice machine,
per the limits stated later in this manual. The
remote condenser may be installed outdoors within
the temperature limits listed below. The
interconnecting tubing must be installed per the
directions stated in this manual, and the amount of
tubing exposed to uncontrolled temperatures must
be minimized.
Space Limitations
Although the machine will function with no
clearance to the top and sides, some space must
be allowed for service access. Building the
machine in with no access will cause higher service
cost, in many cases this extra cost may not be
covered by warranty.
Environmental Limitations, ice machine
:
Minimum
Maximum
Air temperature
50
o
F.
100
o
F.
Water
temperature
40
o
F.
100
o
F.
Water pressure
20 psi
80 psi
Remote condenser
Minimum
Maximum
Air temperature
-20
o
F.
120
o
F.
Power Supply
Minimum
Maximum
208-230 volt
model
198 volts
253 volts
Warranty Information
The warranty statement for this product is provided
separately from this manual. Refer to it for
applicable coverage. In general warranty covers
defects in material and workmanship. It does not
cover maintenance, corrections to installations, or
situations when the ice machine is operated in
circumstances that exceed the limitations printed
above.
Product Information
The machine is a specialized version of a modular
cuber. A modular cuber does not include any ice
storage, it is designed to be placed onto an ice
storage bin. Many installations only require the
matching bin, but some may need an adapter to be
placed between the ice machine and the bin.
Additionally, the machine must be connected to the
correct remote condenser and use the correct
pre-charged tubing. The machine is supplied with a
full refrigerant charge, field charging is not
required.
This product cannot be stacked.