
BC0530 User Manual
March 2020
Page 8
Installation: Water
Drain lines must be installed with a minimum drop of
2.5 cm per meter run (.3 inch drop per foot run).
Ice machine and bin drains may be insulated to
prevent condensation.
Follow all local and national codes.
Connect Drain
Adapt as needed and connect to the 3/4” ID flex drain
out the back of the unit. Do not use flexible tubing
beyond this connection, use only rigid tubing.
Potable Water Supply
There are no specific requirements for water
treatment provided that the water is potable, not
laden with sediment and does not exhibit residual
chlorine level greater than 0.2 ppm. The use of water
treatment, however, may increase the intervals
between cleaning operations.
Do not connect the ice machine to a hot water supply
line. Insulate the water line from sources of heat or to
prevent condensation.
Note: Water temperatures higher than the
recommended maximum will cause reduced capacity.
High residual chlorine (more than 0.2 Ppm) can cause
corrosion of ice maker components. High chlorine
levels must be reduced, in the ice maker water supply,
to protect the equipment and preserve the product
warranty. Please contact your local water conditioning
expert for recommendations, about your specific
water supply, or consult the factory.
A minimum 0.2 MPa (30 psig) dynamic water supply
pressure is required for proper operation of the ice
maker water valve. Minimum water pressure 0.2
MPa (30 psig) Maximum water pressure 0.6 MPa
(100 psig). If a water pressure regulator is used, the
recommended setting is 0.2 MPa to 0.3 MPa (30 to 50
psig) dynamic.
Connect Water Supply
NOTE -
Purge all water supply lines before
connecting them to the ice machine.
Adapt as needed using field supplied fittings and
connect to the 3/4” FPT fitting on the back of the unit.
Minimum tubing size to use is 3/8” OD.