1.8
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20170601
Specifications
Specifications
Compliance
Designed and manufactured under an ISO 9001 certified quality
management system
UL Listed to U.S. and Canadian safety standards (File E212775;
NRGU, NRGU7)
CE Mark
RCM Mark
General
AC Current Inputs
5 A nominal:
15 A continuous, 500 A for 1 s,
linear to 100 A symmetrical, 1250 A
for 1 cycle
Burden:
0.27 VA at 5 A
2.51 VA at 15 A
1 A nominal:
3 A continuous, 100 A for 1 s,
linear to 20 A symmetrical, 250 A for
1 cycle
Burden:
0.13 VA at 1 A
1.31 VA at 3 A
Power Supply
125/250 Vdc or Vac
Range:
85–350 Vdc or 85–264 Vac
Burden:
<25 W
Interruption:
45 ms at 125 Vdc
Ripple:
100%
48/125 Vdc or 125 Vac
Range:
38–200 Vdc or 85–140 Vac
Burden:
<25 W
Interruption:
160 ms at 125 Vdc
Ripple:
100%
24/48 Vdc
Range:
18–60 Vdc polarity dependent
Burden:
<25 W
Interruption:
110 ms at 48 Vdc
Ripple:
100%
Note
: Interruption and Ripple per IEC 60255-11:1979.
Output Contacts
Standard:
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating:
50 A
MOV Protection:
270 Vac/360 Vdc; 130 J
Pickup Time:
<5 ms
Dropout Time:
<5 ms, typical
Breaking Capacity (10,000 Operations):
24 V
0.75 A
L/R = 40 ms
48 V
0.50 A
L/R = 40 ms
125 V
0.30 A
L/R = 40 ms
250 V
0.20 A
L/R = 40 ms
Cyclic Capacity (2.5 Cycles/Second):
24 V
0.75 A
L/R = 40 ms
48 V
0.50 A
L/R = 40 ms
125 V
0.30 A
L/R = 40 ms
250 V
0.20 A
L/R = 40 ms
High-Current Interrupting Option:
Make:
30 A
Carry:
6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating:
50 A
MOV Protection:
330 Vdc; 130 J
Pickup Time:
<5 ms
Dropout Time:
<8 ms, typical
Breaking Capacity (10,000 Operations):
24 V
10 A
L/R = 40 ms
48 V
10 A
L/R = 40 ms
125 V
10 A
L/R = 40 ms
250 V
10 A
L/R = 20 ms
Cyclic Capacity (4 Cycles in 1 Second Followed by 2 Minutes
Idle for Thermal Dissipation):
24 V
10 A
L/R = 40 ms
48 V
10 A
L/R = 40 ms
125 V
10 A
L/R = 40 ms
250 V
10 A
L/R = 20 ms
Note:
Do not use high current interrupting output contacts to switch
ac control signals. These outputs are polarity dependent.
Note
: Make per IEEE C37.90-1989; Breaking and Cyclic Capacity
per IEC 60255-23:1994.
Optoisolated Inputs
Contact inputs have a fixed, 1/4-cycle debounce time
250 Vdc:
Pickup 200–300 Vdc; Dropout 150 Vdc
220 Vdc:
Pickup 176–264 Vdc; Dropout 132 Vdc
125 Vdc:
Pickup 105–150 Vdc; Dropout 75 Vdc
110 Vdc:
Pickup 88–132 Vdc; Dropout 66 Vdc
48 Vdc:
Pickup 38.4–60 Vdc; Dropout 28.8 Vdc
24 Vdc:
Pickup 15.0–30 Vdc
Note
: 24, 48, and 125 Vdc optoisolated inputs draw approx. 4 mA
of current; 110 Vdc inputs draw approx. 8 mA of current; and 220
and 250 Vdc inputs draw approx. 5 mA of current. All current
ratings are at nominal input voltage.
Frequency and Rotation
System Frequency:
50 or 60 Hz
Phase Rotation:
ABC or ACB
Communications Ports
EIA-232:
1 front and 2 rear
EIA-485:
1 rear, 2100 Vdc isolation
Baud Rate:
300–19200 bps
Operating Temperature
–40
to +85
C (–40
to +185
F)
Time-Code Input
Relay accepts demodulated IRIG-B time-code input at Port 1 or 2.
Relay is time synchronized to within ±5 ms of time source input.
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...