2.11
Date Code 20080918
Instruction Manual
SEL-749M Relay
Installation
Rear-Panel Connections
Power Connections
The
POWER
terminals on the rear panel (
A01(+/H)
and
A02(—/N)
) must connect to
110–240 Vac, 110–250 Vdc, or 24-48 Vdc (see
complete power input specifications).
The
POWER
terminals are isolated from chassis ground. Use 16 AWG
(1.5 mm
2
) size or heavier wire to connect to the
POWER
terminals.
For compliance with IEC 60947-1 and IEC 60947-3, place a suitable external
switch or circuit breaker in the
POWER
leads for the SEL-749M; this device
should interrupt both the hot (
H
) and neutral (
N
) power leads. The maximum
current rating for the power disconnect circuit breaker or optional overcurrent
device (fuse) should be 20 A. Be sure to locate this device within 3.0 m (9.8
feet) of the relay.
Operational power is internally fused by a power supply fuse. See
for details. Be sure to use fuses that comply with
IEC 60127-2.
Grounding
(Earthing)
You must connect the ground terminal labeled
GND
on the rear panel to a rack
frame or switchgear ground for proper safety and performance. Use 12 AWG
(4 mm
2
) or heavier wire less than 2 m (6.6 feet) in length for the ground
connection.
Serial Ports
Because all ports (
F
,
2
,
3
, and
4
) are independent, you can communicate to any
combination simultaneously. Although serial
Port 4
on the optional
communications card consists of an EIA-485 (
4A
) and an EIA-232 (
4C
) port,
only one port is available at a time. Use the
Port 4
communication interface
COMMINF setting to select between EIA-485 and EIA-232. Modbus RTU
protocol is available on
Port 3
or
4
, but not both.
The serial port EIA-485 plug-in connector accepts wire size AWG 24 through
AWG 12. Strip the wires 8 mm (0.31 inches) and install with a small slotted-
tip screwdriver. All EIA-232 ports accept 9-pin D-subminiature male
connectors.
For connecting devices at distances over 100 feet, where metallic cable is not
appropriate, SEL offers fiber-optic transceivers or the fiber-optic port. The
SEL-2800 family of transceivers provides fiber-optic links between devices
for electrical isolation and long-distance signal transmission. Contact SEL for
further information on these products.
IRIG-B Time-Code Input
When ordered with optional IRIG-B input, the SEL-749M accepts a
demodulated IRIG-B time signal to synchronize the internal clock with an
external source. Two options for IRIG-B signal input are given, but only one
should be used at a time. IRIG-B (
B01
and
B02
) inputs or an SEL
communications processor via EIA-232 serial
Port 3
may be used. The
available communications processors are the SEL-2032, SEL-2030,
SEL-2020, and the SEL-2100 Logic Processor.
Fiber-Optic Port
The SEL-749M includes a multimode (receive only) with ST connector, fiber-
optic port which is compatible with the SEL-2600 RTD modules.
Contact with instrument terminals
can cause electrical shock that can
result in injury or death.
!
DANGER
The relay contains devices sensitive
to Electrostatic Discharge (ESD).
When working on the relay with the
front panel removed, work surfaces
and personnel must be properly
grounded or equipment damage may
result.
!
CAUTION
Содержание SEL-749M
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...