2.8
SEL-734W and SEL Wireless Current Sensor
Field Reference Guide
Date Code 20191029
Installation
Getting Started
Step 4. Select the
Update SER
button. QuickSet will poll the data from the
SEL-734W and show the data in the window. QuickSet reports the
SEL
OGIC
element name in the SER report. Refer to the appropriate
design template guide to determine the function of the SEL
OGIC
ele-
ment used for capacitor bank control. You can also complete the next
steps to view an aliased SER report.
Step 5. Select the
Aliased SER
button to view an aliased SER report. This
shows the SEL
OGIC
element function, instead of the SEL
OGIC
element name, to the capacitor bank control algorithm. Please refer
to your design template guide for further details.
Validate SER
After the controller operates the bank for the first time, the sequence of events
will be stored in memory. View the SER records as shown in the previous section,
then use the following guidelines to ensure that the controller operated the capac-
itor bank properly.
The enclosure contains one open contact and one close contact to control one
three-phase switch that is electrically connected. The enclosure does not connect
to the switch auxiliary contacts. Use the following guidelines to ensure the con-
troller operates the switches properly.
➤
Verify output contacts operate properly.
➤
Ensure each output contact remains asserted for the configured
duration.
➤
After each operation, ensure the SEL-734W indicates the proper
switch status.
Содержание SEL-734W
Страница 4: ...This page intentionally left blank ...
Страница 6: ...This page intentionally left blank ...
Страница 8: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 36: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 44: ...This page intentionally left blank ...
Страница 46: ...This page intentionally left blank ...
Страница 47: ......