5.8
SEL-700G Relay
Instruction Manual
Date Code 20170814
Metering and Monitoring
Metering
➤
Voltage values (phase, phase-to-phase, synchronism check,
neutral): 7.5 V • PTRn, 13 V • PTRn, 7.5 V • PTRS, and
7.5 V • PTRN, respectively.
➤
Power values (real, reactive, and apparent): All three currents
(I
A
n, I
B
n, I
C
n) and all three voltages (V
A
n, V
B
n, V
C
n, or V
AB
n,
V
BC
n, V
CA
n) must be above their thresholds.
Figure 5.7 shows an example device response to the METER M command.
To reset maximum/minimum meter values, issue the METER RM command
as shown in Figure 5.8. The max/min meter values can be reset from the serial
port, Modbus, the front panel, or assertion of the RSTMXMN relay element.
The date and time of the reset are preserved and shown in the max/min meter
report.
All maximum and minimum metering values are stored to nonvolatile
memory four times per day and within one minute of the maximum and
minimum metering values being reset.
=>>
MET M <Enter>
SEL-700G Date: 02/24/2010 Time: 15:13:20.377
GENERATOR RELAY Time Source: Internal
MAX DATE TIME MIN DATE TIME
IAX (A) 505.2 02/24/2010 15:03:38 504.2 02/24/2010 11:29:14
IBX (A) 502.7 02/24/2010 11:29:28 501.1 02/24/2010 14:58:14
ICX (A) 500.0 02/24/2010 15:01:15 498.1 02/24/2010 11:28:33
IGX (A) 11.7 02/24/2010 11:30:07 4.0 02/24/2010 15:12:28
IAY (A) 501.2 02/24/2010 15:03:38 500.6 02/24/2010 11:29:14
IBY (A) 503.5 02/24/2010 11:29:28 502.3 02/24/2010 14:58:14
ICY (A) 500.1 02/24/2010 15:01:15 499.6 02/24/2010 11:28:33
IGY (A) 10.1 02/24/2010 15:03:14 9.0 02/24/2010 14:59:16
IN (A) 11.1 02/24/2010 15:05:12 9.6 02/24/2010 14:54:15
VAX (V) 9980.8 02/24/2010 15:07:16 9974.7 02/24/2010 15:11:21
VBX (V) 9983.4 02/24/2010 11:29:07 9979.7 02/24/2010 14:51:00
VCX (V) 9987.4 02/24/2010 11:29:45 9983.5 02/24/2010 15:07:59
VS (V) 9985.8 02/24/2010 15:05:13 9975.7 02/24/2010 14:11:24
VN (V) 15.8 02/24/2010 15:03:12 5.7 02/24/2010 14:12:25
VN3 (V) 5.8 02/24/2010 14:05:23 2.7 02/24/2010 14:15:44
VP3X (V) 17.9 02/24/2010 15:05:13 9.7 02/24/2010 12:11:54
kW3X (kW) 13026 02/24/2010 14:54:52 12702 02/24/2010 11:27:49
kVAR3X (kVAR) 8031.6 02/24/2010 11:29:01 7494.6 02/24/2010 14:50:34
kVA3X (kVA) 15033 02/24/2010 15:06:53 15023 02/24/2010 11:29:57
FREQX (Hz)
60.00 02/24/2010 11:22:50 59.98 02/24/2010 15:02:24
RTD1 (C) 91 02/24/2010 15:06:19 -48 02/24/2010 14:50:23
RTD2 (C) 94 02/24/2010 15:06:23 -24 02/24/2010 14:50:23
RTD3 (C) 96 02/24/2010 15:06:27 0 02/24/2010 14:50:23
RTD4 (C) 24 02/24/2010 14:50:22 24 02/24/2010 14:50:23
RTD5 (C) 48 02/24/2010 14:50:22 48 02/24/2010 14:50:23
RTD6 (C) 72 02/24/2010 14:50:22 72 02/24/2010 14:50:23
RTD7 (C) 96 02/24/2010 14:50:22 23 02/24/2010 15:02:59
RTD8 (C) 120 02/24/2010 14:50:22 120 02/24/2010 14:50:23
RTD9 (C) 144 02/24/2010 14:50:22 144 02/24/2010 14:50:23
RTD10 (C) 168 02/24/2010 14:50:22 168 02/24/2010 14:50:23
LAST RESET = 02/24/2010 11:22:49
=>>
Figure 5.7
Device Response to the METER M Command
=>>
MET RM <Enter>
Reset Metering Quantities (Y,N)?
Y
<
Enter
>
Reset Complete
=>>
Figure 5.8
Device Response to the METER RM Command
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...