2.4
SEL-587Z Instruction Manual
Date Code 20020903
Installation
Rear-Panel Connections
Rear-Panel Connections
Connect wiring to the conventional terminal blocks on the relay rear panel.
Make terminal block connections with size #6-32 screws using a Phillips or
slotted screwdriver (see
Section 1: Introduction and Specifications
tightening torque information). You may request locking screws from the
factory. Refer to
to make all terminal block connections. Be sure to
use wire that is appropriate for your installation with an insulation rating of at
least 105°C.
Output contacts OUT1–OUT4 and ALARM are not polarity dependent.
Optoisolator inputs IN1 and IN2 are not polarity dependent.
Connector terminals 101–112 and 201–216 accept wire size AWG 24 to 12.
Ground connection (terminal 217): tab size 0.250" x 0.032", screw size #6-32.
Use 12 AWG (4 mm
2
) or heavier wire less than 6.6 feet (2 m) in length for this
connection.
Figure 2.2
Relay Rear Panel.