Date Code 20020215
Factory-Set Logic
1-25
SEL-351R Instruction Manual
Pin F energized, indicating
that switch SW3 (52b in
close circuit) is closed
(see Figure 7.30)
SW3 (52b) open
and
SW1 (52a) closed
Switch SW1 (52a in
trip circuit) is closed
(see Figure 7.30)
Hot line tag OFF
(see Figure 1.47)
Hot line tag ON
and
No close In progress
Close logic output
(see Figure 6.1)
Close logic output
(see Figure 6.1)
LOCK operator
control ON
and
Serial port
CLOSE Command
LOCK operator control OFF
(see Figure 1.50)
Control in the
reclose cycle state
No close In progess
and
No CLOSE command
and
Control not in the
reclose cycle state
Trip logic output
(see Figure 5.1)
Unlatch
Close
Conditions
SEL
OGIC
Setting
ULCL
Unlatch close
after all auxiliary
contacts (52a
and 52b) change
state (see Figure
7.30)
Input into close
logic (see
Figure 6.1)
This logic
prevents the
CLOSE operator
control
pushbutton from
starting a
pending close
when hot line tag
is ON or LOCK
operator control
in ON (see
Figure 1.39)
DWG: M351R079
Relay
Word
Bits
TRIP
PINF
SW1
LT7
CLOSE
LT4
CLOSE
CC
79CY
Figure 1.21: Unlatch Close Conditions
Figure 1.22 shows the logic for recloser status determination. SEL
OGIC
setting 52A includes the
CLOSE Relay Word bit to hold off the change of state of 52A until the unlatch close logic (see
Figure 1.21) unlatches the close signal output. This assures that the 52b in the close circuit is
open (as indicated by Relay Word bit PINF = logical 0 in Figure 7.30) before the close signal
output is unlatched (CLOSE = logical 0).
SW1
CLOSE
DWG: M351R028
Switch SW1 (52a in
trip circuit) is closed
(see Figure 7.30)
SW1 (52a) closed
and
No close in progress
Close logic output
(see Figure 6.1)
Recloser
Status
SEL
OGIC
Setting
52A
Input into close logic
(see Figure 6.1)
Figure 1.22: Recloser Status Determination
Figure 1.20 through Figure 1.22 all propagate into the close logic (see Figure 6.1). The close
signal output (Relay Word bit CLOSE) is then assigned to the HV FET close output with
SEL
OGIC
recloser control close setting (see Figure 7.30):
RCCL = CLOSE
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...