background image

AR-OH

Installation Instructions

                    

                    

                    

25-0071

Page 1 of 2

SCHWEITZER ENGINEERING LABORATORIES, INC.

2350 NE Hopkins Court • Pullman, WA 99163-5603  U.S.A.

Phone: +1.509.332.1890 • Fax: +1.509.332.7990

selinc.com • [email protected]

                    

                    

Note: 

The AutoRANGER

®

 (AR) must detect a minimum voltage field for normal operation. Therefore, install AR units at least 2 ft 

from other line or pole hardware when applying these units on phase-to-phase system voltages of 7.2 kV or less. Additionally, AR 
units should not be installed in such a way that would allow the product surface to reduce the insulating air gap sufficiently to 
initiate a flash over.

Install the Phase Sensor(s)

                    

                    

                    

                    

                    

                    

                    

                    

                    

                    

CAUTION

Do not extend the spring 
beyond parallel with the 
housing, as shown. Over-
extension of the spring 
may cause a loss of 
clamping force.

                    

Use a hot stick to grasp the 
molded hookeye on the face of 
the phase sensor.

                    

Position the spring clamp 
against the conductor and 
retaining bar, as shown.

                    

Position the indicator with the 
conductor against the retaining 
bar. Release the hot stick.

To ensure optimum FCI function, it is best to follow the FCI distance-to-pole recommendations shown in 

Figure 1

.

                    

                    

Figure 1

Reference A: Maximum recommended distance from pole of 6 feet.

Reference B: Minimum distance from pole of 3 feet.

Reference C: Minimum distance from energized hardware of 2 feet.

7.0 in

(17.8 cm)

3.8 in

(9.7 cm)

6.1 in

(15.5 cm)

Before installation, read and understand all instructions in their 
entirety. For assistance, please contact Customer Service at 
1-847-362-8304 or by email at [email protected].

CAUTION

Install in accordance with normal safe operating practices. These instruc-
tions are not intended to replace or supersede existing safety or operating 
requirements. Only trained qualified personnel should install or operate 
fault indicators and sensors.