Installation Instructions
ATTENTION!
Function reserved for Authorised Assistance
Centres only.
The user is NOT authorised to activate the
function described below.
It is possible to adjust the maximum thermal capacity in heating
mode, by decreasing the burner pressure value.
3.12.1 - ADAPTATION OF THE POwER TO THE HEATING sYsTEM
E.g.
BwA R 50
to decrease the output of the boiler to 35 kW, edit parameter
HP (about 72).
Es:
BwA R 70 c
to decrease the output of the boiler to 50 kW, edit parameter
HP (about 76).
Power Supply (KW)
FH (%)
Act on parameter
HP
(par. 4.2 SE parameters list) to achieve
the value corresponding to the desired output.
BWA R 50
BWA R 70