Parts supplied:
• one (1) thermostat;
• two (2) mounting screws;
• four (4) solderless connectors suitable for copper wires;
• one (1) floor temperature sensor.
2. Installation
Thermostat selection and sensor location
The thermostat must be mounted on a connection box, at
around 1.5 m (5 feet) above the floor level, on a section of the
wall exempt from pipes or air ducts.
Do not install the thermostat in a location where
temperature measurements could be altered. For example:
• close to a window, on an external wall, or close to a door
leading outside;
• exposed directly to the light or heat of the sun, a lamp, a
fireplace or any other heat source;
• close or in front of an air outlet;
• close to concealed ducts or a chimney;
• in a location with poor air flow (e.g. behind a door), or with
frequent air drafts (e.g. head of stairs).
To install the sensor, refer to the installation guide of your
heating floor.
Thermostat mounting and connection
1.
Cut off power supply on lead wires at the
electrical panel in order to avoid any risk of
electric shock. Ensure that the thermostat will
be installed on a junction box located in an
uninsulated wall.
2. Ensure that the air vents of the thermostat are clean and
clear of any obstructions.
3.
Using a screwdriver, loosen the screw retaining the
mounting base and front part of the thermostat. Remove
4