10
DK 600 - 3500 ECO
GB
Assembly dimensions (in mm), see Fig. 2a
Composition and global warming potential of the refrigerant
1)
Global Warming Potential
2)
Compared to a value of 1 for carbon dioxide over 100 years
Reference conditions according to DIN/ISO 7183
Correction factors
For other operating pressure p
1
, multiply the volume flow by factor f
1
:
For other compressed air inlet temperature t
1
, multiply volume flow by factor f
2
:
For other cooling air temperature t
c
, multiply volume flow by factor f
3
:
For other pressure dew point t
pd
, multiply volume flow by factor f
4
:
H
W
D
D1
D2
D3
H1
H2
H3
A
A1
A2
A3
A4
DK 600 ECO
DK 985 ECO
DK 1500 ECO
745 325 263 289 150 ---
15
405 ---
110 45
50
145 90
DK 2200 ECO
DK 3500 ECO
845 410 415 375 ---
289 32
---
87
130 45
40
170 75
Substance
Proportion
(%)
GWP
1)
R134a
HFKW 134a
100
1300
2)
Temperature
20
°C
Operating pressure p1
7
bar
Compressed air inlet temperature 35
°C
Cooling air temperature
25
°C
Pressure dew point
3
°C
p
1
(bar) 3
4
5
6
7
8
9
10
11
12
14
16
f
1
0.75 0.85 0.90 0.95 1.00 1.04 1.07 1.10 1.12 1.14 1.18 1.20
t
1
(°C)
30
35
40
45
50
f
2
1.25
1.00
0.85
0.75
0.60
t
c
(°C)
25
30
35
40
45
f
3
1.00
0.96
0.92
0.88
0.80
t
pd
(°C) 3
5
7
9
f
4
1.00
1.2
1.35
1.45