8.2  Error message, warning and status indication

Prog_01

Prog_02

Prog_03

Prog_04

Display indications  

(depending on the  

application program)

Comment

Error -  
operating mode selection

Both inputs on which the operating mode selector switch is connected have the same signal 
(both HIGH or both LOW).

Error - single-channel  
opening detected

With a 2-channel sensor a 1-channel drop is detected. A restart is only possible if the sensor 
is 2-channel open and then back to 2-channel closed

Error -  
antivalent safety switch

With a 2-channel equivalent sensor (2 NC) nonequivalence is detected. (Instead of 2 identical 
signals one signal is opposite, for example, channel A = HIGH and channel B = LOW)  
OR with a 2-channel nonequivalence sensor (1 NC and 1 NO) an equivalence is detected. 
(Instead of 2 different signals, both signals are the same)

Error - dual-channel control 
when single-channel is selected

The inputs for sensors (e.g. I02 and I03) were set as 1-channel sensors (MSP Code,  
3rd place = 2). On the deactivated odd input (here I03) a high signal is detected.

Error - control of a disabled 
sensor

The inputs for sensors (e.g. I04 and I05) were not needed for the safety circuit and are set as 
deactivated. At one or both inputs a HIGH signal is detected.

Error - feedback circuit (EDM)

The safety circuit is closed and the safe outputs are open: To restart the safety monitoring 
the high signal is absent at the corresponding input, which means the feedback loop of the 
integrated actuator is not closed.

Timeout -  
Disturbed safety switch

The time lag between the signal changes of the two channels of a 2-channel sensor was 
larger than the set monitoring time.

Error - Muting

A fault was detected in the muting sequence, which led to a halt (see fault case muting). 
Eliminate problem, press Override and confirm with START / RESET.

Warning -  
Interlock not locked

Setting the solenoid interlock parameters, for example, via the inputs I06 and I07:  
The interlock (magnet) is driven, but the interlock does not lock.

Warning -  
Safety circuit open

Part or all of the connected sensor is / are not yet closed.

Warning - Analogue Input: 
Emergency-Stop active

After exceeding the limits AI0-3 and AI1-3, an Emergency-Stop function was activated and the 
safe outputs were switched off.

Warning-  
RESET necessary

The safety circuit is closed. To restart the safety monitoring the START / RESET is missing.

Warning -  
Analogue input:  
Interlock not released

When setting solenoid interlock parameters, for example, via the inputs I06 and I07 and 
setting the limit parameters of AI0-0 and AI 1 0: After the limits AI0-0 and AI 1 0 are exceeded, 
the solenoid interlock can be unlocked via the corresponding input. If an unlock request is trig-
ger via the corresponding input and the limit AI0-0 and AI1-0 are not reached, then a warning 
message is triggered.

Manual operation is active

At the inputs where the operating mode selector switch is connected, the position "Manual" 
has been detected, i.e. I00 = LOW and I01 = HIGH.

Содержание PROTECT SELECT

Страница 1: ...neral information for electrical connection 4 4 2 Power supply 4 4 3 Start level 4 4 4 Sensor level 4 4 5 Actuator level 5 5 Operating principle and settings 5 1 Connection operating elements 6 5 2 De...

Страница 2: ...se If used incorrectly or not for the intended purpose or in the case of tampering danger to persons or damage to machine and system parts from using the safety module cannot be ruled out 1 7 Exclusio...

Страница 3: ...t change Sinusoidal max 2 8 Hz max 50 mA s Input resistance 10 k Safe analogue inputs Category PL SIL CL Single channel If a cable break dominates Cat 3 PL d SIL CL 2 Dual channel Cat 4 PL e SIL CL 3...

Страница 4: ...d pins Electrical power cables must be routed separately from communication lines 3 2 Disassembly Unlock the bottom of the enclosure by means of a slotted screwdriver push up and hang out slightly til...

Страница 5: ...onductor outputs Q2 Q3 with 24 VDC 2 x safe relay outputs QR1 QR2 with common supply QR0 up to 250 VAC or 24 VDC 4 x operational optional message outputs Y0 Y 3 with 24 VDC Relay outputs 250 V 24V GND...

Страница 6: ...y outputs Operational outputs signalling output Clock outputs for the supply of safe digital inputs for short circuit recognition 5 3 Start level Alternatively auto start or manual start falling edge...

Страница 7: ...processor MSP which is parameter assigned by a three digit hexadecimal number The 1 position describes the sensor the 2 position the additional function and the 3 position the contact properties The e...

Страница 8: ...ing locked guard interlocks Power to lock For solenoid locked guard interlocks The interlock type always applies to all connected guard interlocks Analog inputs Dual Sensor 2 channel analysis of AI0 a...

Страница 9: ...the list After entry a plain text display of the selected settings appears ENTER moves back to the code list display If you navigate up with the last MSP code the next menu appears MSP 01 1 A 5 MSP 0...

Страница 10: ...leshooting Description of possible error cause and rectification measures Restart Trigger of a new start once the error has been eliminated Configuration Enter PIN Entry of the PIN codes so as be able...

Страница 11: ...essary Sensors and emergency stop command devices can be reset in any order Sensor level Safe analogue inputs Implemented in the following application programs for both analogue secure inputs are the...

Страница 12: ...ital inputs I00 I01 Operating mode selector switch automatic I00 HIGH I01 LOW manual I00 LOW I01 HIGH I02 I03 Enabling switches MSP 6 Default value 0 0 0 I04 I05 1 sensor MSP 2 Default value 0 0 0 I06...

Страница 13: ...ayed Signalling output Y3 error message status indication Manual mode Flashing with 2Hz Warning Flashing with 1Hz Error messages Lights up Safe semi conductor outputs Q0 Q0N Stop 0 or Stop 1 All semic...

Страница 14: ...lay outputs QR1 QR2 Stop 0 or Stop 1 All relay outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Application...

Страница 15: ...4 sensor MSP 5 Default value 0 0 0 I10 I11 5 sensor MSP 6 Default value 0 0 0 I12 I13 Feedback circuit I14 I15 START RESET or latch interlock for I16 I17 I16 I17 Emergency stop command device MSP 1 De...

Страница 16: ...00 Monitoring time for MSP 5 T11 10 00 Monitoring time for MSP 6 T12 10 00 Stable time for MSP 1 E Stop T13 0 10 Stable time for MSP 2 T14 0 10 Stable time for MSP 3 T15 0 10 Stable time for MSP 4 T1...

Страница 17: ...conductor outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Safe relay outputs QR1 QR2 Stop 0 or Stop 1 All...

Страница 18: ...The muting monitoring time continues The muting lamp Y0 remains on The muting outputs remain set e The workpiece releases the light barrier AOPD The muting monitoring time continues The muting lamp Y0...

Страница 19: ...art the safety monitoring the high signal is absent at the corresponding input which means the feedback loop of the integrated actuator is not closed Timeout Disturbed safety switch The time lag betwe...

Страница 20: ...56 12103 Berlin ID n 0035 Person authorized for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal K A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal P...

Отзывы: