Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
Control box Control NT
Version: 27248 - C
10
Subject to technical changes
4.2.1
Feedback contact
Note:
Outputs 1 and 2 can be used for both mains power and low voltage (e.g. 24V).
If one of the two outputs is used for the mains voltage, the other output must
not
be used
for low voltage.
4.2.2
Control contacts
Decive enable
Note:
Input 3 must not be connected with the mains voltage or with low voltage. It may
only be connected with a floating switching element.
BUS connection
Button and latching N/O contact
4.2.3
Adjustable functions
Runtime and configuration of DIP switches
1
Pump ON
Floating N/O contact (Relay contact)
2
Malfunction / service Floating N/O contact (Relay contact)
3
Enable
Input for a floating latching switching contact, for example
Shutter control. The switching device is active when the con-
tact is closed. In state as supplied the contact is "closed" with a
wire bridge.
4
BUS A
BUS B
Interface für Betrieb via Bus. Connection is protected against
polarity reversal. For address setting see section 4.4.
5
24V
Connection terminals for button lighting.
Configurable, see section 4.4 Pos.5.
OFF - LED lit continuously
ON - Flash 3x when the device switches
The factory setup is OFF
6
24 V
START/STOP
Connection terminal for piezo buttons or latching N/O contact.
Both switching contacts must always be floating.
For activation see section 4.4.
7
Interval
Potentiometer for setting the runtime (1 - 60 minutes)
8
CONFIG
DIP switches for setting the device address and switch functio-
nality. See section 4.4.