ExMax-...-F, ExMax-...-SF, RedMax-...-F, RedMax-...-SF
PA
PA
ExMax-...-BF, RedMax-...-BF
PA
PA
PA
U
0
= 10,6 V
I
0
= 11 mA
P
0
= 30 mW
C
i
= 0
L
i
= 0
IIC
IIB
IIA
C
0
830 nF 3,7µF 4,5 µF
L
0
2 mH
5 mH 10 mH
Wiring alternatives for on-off and 3-pos actuators with spring return
On-off and 3-pos
1
2
3
4
~
-
~
+
PE
heater
24 to 240 VAC/DC
a
b
If 40 sec. or 60 sec. mode is selected for
motor and/or spring return, the self ad
justment of angle of rotation must be
started.
Never use actuators without external
torque/force min. 10 Nm.
Attention
!
!
On-off 1-wire
1
2
3
4
~
-
~
+
PE
heater
24 to 240 VAC/DC
a
Wiring alternatives for BF actuators
On-off 1-wire spring Ex-i circuit
1
2
°C
push button
5 6
< 5 °
7
8 9
> 85 °
10
1
2
3
~
-
~
+
PE
heater
24...240 VAC/DC
ExPro-TT
4
O-off/3-pos spring Ex-i circuit
1
2
°C
5 6
< 5 °
7
8 9
> 85 °
10
1
2
3
~
-
~
+
PE
heater
24...240 VAC/DC
ExPro-TT
4
a
b
On-off 1-wire spring Ex-d limiter
1
2
°C
Push button
The intrinsic safe circuit must
be closed otherwise the
actuator is unable to work!
5 6
< 5 °
7
8 9
> 85 °
10
1
2
3
~-
~+
PE
heater
24...240 VAC/DC
4
Limiter
Values of the Ex-i circuit
Attention
!
!
EXC-DS1/VA
If 40 sec. or 60 sec. mode is selected for
motor and/or spring return, the self adjust
ment of angle of rotation must be started.
Never use actuators without external
torque/force min. 10 Nm.
Attention:
If you use this type of
wiring the heater does
not work in case of
open contact.
Attention:
If you use this type of
wiring the heater does
not work in case of
open contact.
Attention:
If you use this type of
wiring the heater does
not work in case of
open contact.
Integrated aux. switches
max 24 V/3 A, 240 V/0,5 A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
Integrated aux. switches
max 24 V/3 A, 240 V/0,5 A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
Integrated aux. switches
max 24 V/3 A, 240 V/0,5 A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
Ex-i circuit for
p potential free
push button on site
and safety temperature sensor
(Type
ExPro-TT-..
accessories)
Ex-i circuit for
p potential free
push button on site
and safety temperature sensor
(Type
ExPro-TT-..
accessories)
push button
B
A
B
A
B
A
SB 1.0
SB 1.1
SB 7.3
SB 7.4
SB 7.5
ExMax-.. and RedMax-.. extra information EL size M
Schischek GmbH
Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail [email protected]
www.schischek.com
E X P L O S I O N P R O O F