10-position switch (S)
Push button (T)
3-colour LED

Switch – Push button – Lamp 

for adjustment (behind the blanking plug)

Extra information for 

...Max

 actuators  –  

size M

for optimization of planning, installation and initial startup for safe operation

Assembly

Electric

 Dimensions

 Outdoor installation

 Control elements: switch – push button – LED

 Power supply design

 Line cross sections

 Problem treatment/error indication

 Dimensions, drill plate

 Control elements: switch – push buttons – LED

 Outdoor installation

 Mounting on air dampers (form-fit)

 Mounting on fire dampers (form-fit)

 Mounting on butterfly valves and ball valves

 Mounting of terminal box ...Box 

  and auxiliary switch ...Switch

Dimensioning in mm

inclusive

bend radius

of cables

Double square 16 × 16 mm

All actuators are equipped with a 10-position switch, a push button and a multicolour LED 

for calibration. These control elements are to be found cable-laterally behind the two middle 

sectioned dummy plugs. For operation these must be removed. The calibration can be 

achieved despite lining up power supply at the actuator. The explosion prevention is not 

impaired thereby. However, it has to be of great concern that the dummy plugs must be 

rescrewed in order to comply with the IP-protection class.

The operation of the switch and button has to be done by means of a small screwdriver. 

Force with strong pressure and /or rotation is to be avoided in any case, since otherwise 

control electronics can be damaged irreparably. Adjustments of torque and running time 

can be achieved also before mounting. The adjustment of angle of rotation can be started 

only with an outside load and accurate mounting.

When mounting actuator outdoors it has to be certain that the actuator is protected against 

direct sun exposure (heat and UV!), rain and snow by employing an enclosure roof. Supply 

voltage is to be applied immediately after mounting in order to assure integrated heating 

at start. 

Since actuators must have an internal temperature fuse, they may not be exposed to a too 

high temperature, neither at storage nor during operation. Otherwise the fuse could respond 

and switch off the actuator irreversibly.

Top side “R”

Bottom side “L”

1 / 6

Содержание ExMax-50.75

Страница 1: ...alibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despite lining up power supply at the actuator The explosion prevention is not impaired thereby However it has to be of great concern that the dummy plugs must be rescrewed in order to comply with the IP protection class T...

Страница 2: ... 180 Furthermore it is to be considered that the actuators have a total angle movement of approx 95 in order to realize a pretension on the control element damper or the like Therefore the actuator sits tilted on the damper shaft Attention Mount with appropriate safety precautions only The drive shaft may only be mechanically adjusted either with the provided socket wrench or the optional accessor...

Страница 3: ...igger is mounted directly to the duct or damper wall with pre assembled tapping screws The position of the safety elements must guarantee free air flow Pro TT is mounted to the actuator by means of quick fastener M12 Connection of safety temperature trigger Pro TT Mounting 1 Affix tap holes M8 in accordance with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actu...

Страница 4: ... M A Screw mounting bracket MKK M with 4 screws to actuator B Screw terminal box to mounting bracket Mounting of terminal boxes Box to actuator via mounting bracket MKK M accessory Terminal box mounted above the actuator Terminal box mounted beside the actuator Mounting bracket can be mounted every 90 A Place square connection part on actuator s shaft B Mount Switch and fix it with screws Mounting...

Страница 5: ...occur due to line resistances As a consequence with 24 VAC DC the actuator receives a too low tension and does not start In order to prevent this the cross section of the inlet line is to be dimensioned accordingly The accompanying formulas allow the calculation of the necessary line cross section respectively maximal permitted conduit length respectively utilizing the existing line cross section ...

Страница 6: ...s section or power supply Ensure that a constant voltage supply is applied on conductor 1 2 Wait until the required operating temperature is achieved by the actuators internal heating system The actuator will start operating independently Readjust correct circuit Adjust a higher torque at the actuator if possible otherwise exchange for a type with higher torque Examine rule and adjusting signals a...

Отзывы: