Chapter 6
– Settings
Recommendation for commissioning:
For commissioning it is recommended to select a value
between
“010” = 1 second and “020” = 2 seconds. This
eliminates an early triggering of the filter.
Afterwards the filter time may be reduced.
Recommendation for applications with Profisafe:
In applications with Profisafe the filter time should be set
higher than the SIL monitor time at Profisafe.
Please observe:
The higher the filter time is selected the later as bus
error is indicated (max. only as long as the selected SIL
monitor time). Please verify therefore if your application
meets the required safety criteria with the selected filter
time.
Select
Filter time
Exit menu
Press the button
< arrow right >
until the cursor is
placed below the first digit of the filter time.
Select a filter time by using the buttons
< arrow up >
and
< arrow down >
. Use the buttons
< arrow right >
and
< arrow left >
to place the cursor below the
correct digit.
Press the button
<Enter>
.
The data will be saved and the cursor is placed below
the first digit in field A.
Press the button
<ESC>
.
You have now completed Step 3 and all required
PROFIBUS settings are done.
Assembly and commissioning instructions DATAEAGLE 3000
6-17