Chapter 6
– Settings
If you don
’t want to use the diagnostic function enter the
following addresses:
Diagnostic slave address = 127
Diagnostic master address = 127
Press the button
<Enter>
The new addresses will be saved.
In the next step the profibus addresses behing the radio
link have to be set. The display shows:
Field A
Field B
Field C
Addressing and
filter setting
01: SA:003 MA:02
Filter: 010x0,1s
Field D
Field A = Position in the table
Meaning of the
fields
The WP-3000 administrates all DP slaves which are
addressed by wireless data in a table. One DP slave address
can be entered in each table position (see field B).
Max. 32 table positions exist. The allocation of the DP slave
addresses to a table position is freely selectable. Gaps are
allowed.
A different amount of DP slaves may be addressed in the
different device versions 3xx2 to 3xx5.
3xx2: 7 DP diagnostic slave
3xx3: 4 DP diagnostic slave
3xx5: 3 DP diagnostic slave
Assembly and commissioning instructions DATAEAGLE 3000