background image

22

2021-07-15 / V1.0

Maintenance

Contactors C320K/C320S – Installation and Maintenance Manual

8.  Maintenance

Note the expert knowledge which is essential for car-

rying out maintenance work, referred to in chapter  

“2. General and safety information”

8.1  Safety

  DANGER

The contactors are used for high voltage switching. Contact with live electrical parts can result in 

serious injuries or even death! 

Live parts are all metal parts belonging directly to one of the circuits or wires connecting to them. 

All other visible metal parts and wiring may also be live if a fault exists.

Before starting any work on the contactors, always comply with the following safety rules:

 

X

Disconnect on all sides

 

X

Secure to prevent switching back on

 

X

Clearly identify the working area

 

X

Check that a voltage-free state exists

 

X

Earth and short circuit; this includes discharging any capacitors in the main circuit 

 

X

Besides the main power circuits, also disconnect additional and auxiliary circuits

 

X

Cover or insulate adjacent live parts

 

X

The presence of a voltage-free state can only be clearly identified by a qualified electrician.

 

X

When the work has been concluded, follow the procedure in reverse.

8.2  Preventive maintenance

Contactors of the C320 series are maintenance-free 

within the rated mechanical life time. The electrical life 

time depends on the number of switching cycles under 

heavy load conditions and may vary for different ap-

plications. In normal use, this corresponds to a decade-

long operating period.

Intervals for regular tests/checks

To ensure the correct function and a prolonged opera-

tional life span of the contactors, the following checks 

and maintenance must be regularly performed.

Test/check

Interval

External visual inspection of the 

contactor

 

X

1x per year

Check of the main contacts (both,  

stationary and moving contacts) 

 

X

1x to 2x  

per year

Checking of the auxiliary switches

 

X

Every 2 years

If the contactors are operated in a particularly dirty 

environment, the visual checks should be performed 

at shorter intervals. Dirt can impair the clearance and 

creepage distances, which can result in a shorter ser-

vice life or to a malfunction.

Extraordinary checks need only be carried out if there 

has been a significant and extraordinarily high record-

ed number of switching cycles under short-circuit con-

ditions.

  DANGER

If damage to the contactor, wires or bus-

bars is visible, the safety of the contactor 

is no longer guaranteed.

 

X

Immediately submit any damaged 

contactors or components for 

maintenance.

Содержание C320 Series

Страница 1: ...3 3 Contactors C320 series 1 pole AC and bi directional DC NO contactors for 1 000 A Installation and maintenance instructions Manual C320 M en...

Страница 2: ...ns 6 3 1 Electrical hazards 6 3 2 Other hazards 6 3 3 Measures for avoiding damage and malfunctions 7 4 Product information 8 4 1 C320 1 pole bi directional DC NO contactors 8 4 2 Technical informatio...

Страница 3: ...required 16 Connecting the S870 auxiliary switches 17 Connecting the coil 18 Connecting the main contacts 19 7 3 Checks 21 8 Maintenance 22 8 1 Safety 22 8 2 Preventive maintenance 22 Intervals for re...

Страница 4: ...methods to simplify working or indicates informa tion of particular importance This manual describes single pole contactors of the fol lowing types C320K 1000 C320S 1000 2 General and safety informati...

Страница 5: ...ons defined in the cor responding technical data sheets or in our C320 catalogue may be overridden The C320 catalogue is available under https www schaltbau com media C320_en pdf X The contactors may...

Страница 6: ...e main circuit X Besides the main power circuits also disconnect additional and auxiliary circuits X Cover or insulate adjacent live parts X The presence of a voltage free state can only be clearly id...

Страница 7: ...estroy the data on the magnetic strips of credit or similar cards X Keep credit or similar cards away from the contactors ATTENTION During switching off strong electromagnetic fields are generated in...

Страница 8: ...breaking capacity are important fea tures of the new contactor X Compact dimensions high rated insulation volt age Ui up to 1 800 volts X High making capacity Icm of up to 3 000 amps and an excellent...

Страница 9: ...acts connection M8 torque 10 12 Nm C Base plate with 4 fastening holes for M5 screws torque 2 3 2 7 Nm D Fixing lugs for bundling and fixing control wires with cable ties E Auxiliary switch S870 W1D1...

Страница 10: ...M8 torque 10 12 Nm C Base plate with 4 fastening holes for M5 screws torque 2 3 2 7 Nm D Fixing lugs for bundling and fixing control wires with cable ties E Auxiliary switch S870 W1D1 t flat plug conn...

Страница 11: ...ing is not available care must be taken to pack the contactor in a way that prevents dam age during shipment 6 Unpacking 6 1 Unpacking the device X Before opening the packaging perform a visual inspec...

Страница 12: ...aded holes for threaded screws or through holes for threaded screws and nuts X Fastening of the contactors on the mounting plate is performed using four M5 mounting screws The length of the mounting s...

Страница 13: ...currents produces elec tric arcs and it is possible that plasma will escape from the openings of the arcing chambers There fore it is extremely important to maintain the minimum clearances to ground e...

Страница 14: ...Tools required X Socket spanner set hexagon nuts X Open ended spanner set X Torque wrench X Hex key set Installing the contactor X Ensure that the contact surfaces on the mounting plate 3 are free fr...

Страница 15: ...able under https www schaltbau com media C320_en pdf X The connecting wires of the main power circuit must be fitted with appropriate ring terminals for M8 terminal screws X Schaltbau recommends Schno...

Страница 16: ...s includes discharging any capacitors in the main circuit X Besides the main power circuits also disconnect additional and auxiliary circuits X Cover or insulate adjacent live parts X The presence of...

Страница 17: ...s caused by the wires e g shock vibrations acting on the terminals X Route the coil control wires 1 to the auxiliary switches 2 X Plug the pre assembled control wires with the re ceptacles 1 to the co...

Страница 18: ...o such diode is used in your control circuit ATTENTION X Mechanically secure the control wires to mi nimise feedback effects of forces caused by the wires e g shock vibrations acting on the terminals...

Страница 19: ...ction with wires are shown in Fig 13 and Fig 14 X Route the pre assembled connecting wires to both main contacts 4 X Screw the 4 ring terminals 3 in place from above using the terminal screws 1 nuts 5...

Страница 20: ...he busbars 3 to both main contacts 4 X Screw the busbars 3 to the main contacts 4 us ing the terminal screws 1 nuts 5 and suitable screw locking elements 2 Schaltbau recommends using Schnorr washers o...

Страница 21: ...ect polar ity X Check that the control wires are correctly connect ed to the auxiliary switches Check the correct assignment and function of the auxiliary switches using a continuity tester X Switch t...

Страница 22: ...the procedure in reverse 8 2 Preventive maintenance Contactors of the C320 series are maintenance free within the rated mechanical life time The electrical life time depends on the number of switching...

Страница 23: ...ace missing fastening elements X tighten the terminal screws to the rated torque Contactor housing Check for X dirt X loose or missing fastening elements penetrations holes in the housing wall X damag...

Страница 24: ...e nance Replacing the S870 auxil iary switches Checking the main contacts The housing of the contactor has inspection openings on both narrow sides 1 through which the main con tacts can be inspected...

Страница 25: ...ls required Continuity tester Procedure X Pull off the receptacles of the control wires from the auxiliary switches X Carefully release the snap fit hook 1 of the catch mechanism Be careful not to dam...

Страница 26: ...6 2021 07 15 V1 0 Maintenance Contactors C320K C320S Installation and Maintenance Manual 1 1 2 2 Fig 21 C320S Replacing the auxiliary switches 1 2 3 3 2 Fig 22 C320S Replacing the auxiliary switches 2...

Страница 27: ...vailable under https www schaltbau com media C320_en pdf 11 Disposal This product is designed for exclusive professional use by commercial companies The owner is responsible for ensuring an environmen...

Страница 28: ...mmunications engineering MIL connectors Charging connectors for battery powered machines and systems Connectors for railway engineering including UIC connectors Special connectors to suit customer req...

Отзывы: