Maintenance

Contactors C193/C294 – Installation and Maintenance Instructions

8.  Maintenance

Note the expert knowledge which is essential for car-

rying out maintenance work, mentioned in chapter 

“2. General and security information”.

 

8.1  Safety

  DANGER

The contactors are used to switch voltage. The touching of electrically conducting parts may result 

in serious injuries or even death! 

Energized parts are all metal parts belonging directly to one of the circuits or wires leading there. All 

other visible metal parts and wires may also be energized in the case of a failure. 

Before beginning any work on the contactors, always observe the following safety regulations:

 

X

Disconnect on all sides

 

X

Ensure that it is not possible to reconnect unintentionally

 

X

Clearly mark your work area

 

X

Make sure that there is no voltage present

 

X

Earth and short circuit the installation; this also includes the discharging of any capacitors in 

the main circuit

 

X

Besides the main electric circuit, also disconnect additional and auxiliary circuits

 

X

Cover or insulate adjacent energized parts

 

X

Only an electrically skilled person may determine if there is no voltage present

 

X

When the work has been concluded, proceed the other way round.

8.2  Preventive maintenance

Contactors of the C193 and C294 series are mainte-

nance-free within the rated mechanical life time. The 

electrical life time depends on the number of switch-

ings under heavy load conditions and may vary for dif-

ferent applications. In normal use, this corresponds to a 

decade-long operating period.

Intervals for regular checks

To ensure the correct function and a prolonged opera-

tional life span of the contactors, the following checks 

and maintenance must be performed regularly.

Checks

Interval

Visual inspection of the contactor 

from outside

 

X

1x per year

Inspection of the auxiliary switch

 

X

Every 2 years

If the contactors are operated in particularly dirty envi-

ronments, the checking intervals for visible inspections 

should be shortened, because dirt can impair the insu-

lation clearances and there is therefore the possibility 

of a shorter service life or an operational fault.
Extraordinary services need only be carried out if there 

has been a significant and extraordinary recorded num-

ber of switchings under fault conditions.

  DANGER

When damages on the contactor, cables 

or busbars are visible, the safety of the 

contactor is no longer guaranteed.

 

X

Immediately give damaged con-

tactors or components to correc-

tive maintenance.

NOTICE

Detent-edged rings and detent-edged washers have 

a limited life time. After 3 times opening of screws 

secured with detent-edged rings or detent-edged 

washers, the rings or washers must be replaced by 

new ones.

 

X

Record the frequency of screw opening in the 

work log.

 

X

After 3 times opening of screws, replace detent-

edged rings or detent-edged washers by new 

ones.

Содержание C193 Series

Страница 1: ...3 3 Contactors C193 C294 series Single and double pole NO contactors Installation and maintenance instructions Manual B193 B294 M en...

Страница 2: ...ntended use 5 2 4 Ambient conditions 5 3 Dangers and security measures 6 3 1 Electrical dangers 6 3 2 Other dangers 6 3 3 Measures for avoiding damages and malfunctions 7 4 Product information 8 4 1 C...

Страница 3: ...contactor 14 DIN rail mounting only C193 series 14 7 2 Electrical installation 15 Electrical data and further technical specifications 15 Preliminaries 15 Safety 16 Required tools and auxiliaries 16 C...

Страница 4: ...work or to particu larly important information This manual refers to NO contactors of the following types C193 single pole C294 double pole This manual describes only stock items of the above mention...

Страница 5: ...ient conditions etc may be changed The catalogues are available under https www schaltbau com en media library X X The contactors may only be used when all protec tive devices are present have been in...

Страница 6: ...y capacitors in the main circuit X X Besides the main electric circuit also disconnect additional and auxiliary circuits X X Cover or insulate adjacent energized parts X X Only an electrically skilled...

Страница 7: ...ets can de stroy data on credit cards or similar cards X X Keep credit cards or similar cards away from the contactors NOTICE During the switching off strong electromagnetic fields are generated in th...

Страница 8: ...ion system components of high reliability which have an electrical life that is above average 4 2 Special features X X Suitable for years of continuous duty X X Intended for high ambient temperatures...

Страница 9: ...gon head bolts M5 load washers tightening torque 3 Nm max Alternative version main contact terminals with hexagon head bolts inch thread 10 24UNC x 3 8 load washers D Mounting holes for screws M4 Tigh...

Страница 10: ...C Main contacts terminals hexagon head bolts M5 load washers tightening torque 3 Nm max Alternative version main contact terminals with hexagon head bolts inch thread 10 24UNC x 3 8 load washers D Mo...

Страница 11: ...be taken to pack the contactor in a way that prevents damage during shipment 6 Unpacking 6 1 Unpack the device X X Before opening the packaging perform a visual inspection for any signs that could in...

Страница 12: ...8 M4 or 4 5 39 max 2 0 Nm Fig 3 C193 series Dimensions in mm and arrangement of the mounting holes 84 M4 or 4 5 47 max 2 0 Nm Fig 4 C294 series Dimensions in mm and arrangement of the mounting holes X...

Страница 13: ...fer to the dimen sion drawings in our catalogues B193 and B294 for minimum clearance upwards and to all sides The catalogues are available under https www schaltbau com en media library Ventilation re...

Страница 14: ...X X Then tighten the four screws 4 with the required torque of 2 Nm max 5 4 3 max 2 0 Nm Fig 6 Install the contactor to the mounting plate the figure shows the C193 series the procedure for the C294 s...

Страница 15: ...efer to our catalogues B193 and B294 The catalogues are available under https www schaltbau com en media library X X The wires of the main current circuit must be fit ted with appropriate ring cable l...

Страница 16: ...Earth and short circuit the installation this also includes the discharging of any capacitors in the main circuit X X Besides the main electric circuit also disconnect additional and auxiliary circui...

Страница 17: ...permissible X X Move and lay the control wires and flat recep tacles only in plugging direction see Fig 8 and Fig 9 X X Attach the control wires mechanically in order to minimize retroactivities e g s...

Страница 18: ...ermissible X X Move and lay the control wires and flat recepta cles only in plugging direction see Fig 10 and Fig 11 X X Attach the control wires mechanically in order to minimize retroactivities e g...

Страница 19: ...n in Fig 12 and Fig 13 X X Lay the prepared wires 3 to both main contacts 1 X X Put the ring cable lugs 2 on the main contacts 1 X X Screw the ring cable lugs 2 with the terminal screws 4 and washers...

Страница 20: ...ews and washers Schaltbau recommends Schnorr Washers or similar to secure the screws X X Connect the connecting bars 6 or angled con necting bars 8 to the main terminals 1 using the terminal screws 4...

Страница 21: ...the control wires are properly connect ed to the auxiliary switch Use a continuity tester to check that the wiring is correct and the auxiliary switch is functioning cor rectly X X Perform several act...

Страница 22: ...n the rated mechanical life time The electrical life time depends on the number of switch ings under heavy load conditions and may vary for dif ferent applications In normal use this corresponds to a...

Страница 23: ...housing Check for X X dirt X X damage or wear and tear X X penetrations holes in the contactor housing wall X X loose or missing fastening elements In case of faults X X remove existent dirt X X if t...

Страница 24: ...n the self locking nut 1 and remove it to gether with the washer X X Remove the auxiliary contact 2 and the screw 3 from the housing X X Insert the new screw 3 in the housing X X Push the new auxilary...

Страница 25: ...media library The updated catalogues render the previous issues in valid 11 Disposal This product is designed for exclusive professional use by commercial companies The owner is responsible for ensur...

Страница 26: ...26 2019 08 07 V1 0 Notes Contactors C193 C294 Installation and Maintenance Instructions Notes...

Страница 27: ...27 2019 08 07 V1 0 Contactors C193 C294 Installation and Maintenance Instructions Notes...

Страница 28: ...wer supplies Contactors for railway applications Terminal bolts and fuse holders DC emergency disconnect switches Special contactors to suit customer requirements Electrics for rolling stock Equipment...

Отзывы: