Volumetric flow controller VAQS
®
08/23 - 8
Construction subject to change.
No return possible!
09.05.2019
Version:
Volumetric flow range for VAQS
®
When the air volume drops below the V
min
shown in the chart,
the correct functioning of the volumetric flow controller is no
longer guaranteed!
Volumetric flow range
H
V
B
(mm)
(mm)
100
150
200
250
300
350
400
500
600
700
800
900
1000
100
min.
(m
3
/h)
36
54
72
90
108
126
144
180
216
-
-
-
-
[l/s]
10
15
20
25
30
35
40
50
60
-
-
-
-
max.
(m
3
/h)
432
648
864
1080
1296
1512
1728
2160
2592
-
-
-
-
[l/s]
120
180
240
300
360
420
480
600
720
-
-
-
-
200
min.
(m
3
/h)
-
-
144
180
216
252
288
360
432
504
576
-
-
[l/s]
-
-
40
50
60
70
80
100
120
140
160
-
-
max.
(m
3
/h)
-
-
1728
2160
2592
3024
3456
4320
5184
6048
6912
-
-
[l/s]
-
-
480
600
720
840
960
1200
1440
1680
1920
-
-
300
min.
(m
3
/h)
-
-
-
-
324
378
432
540
648
756
864
972
1080
[l/s]
-
-
-
-
90
105
120
150
180
210
240
270
300
max.
(m
3
/h)
-
-
-
-
3888
4536
5184
6480
7776
9072 10368 11664 12960
[l/s]
-
-
-
-
1080
1260
1440
1800
2160
2520
2880
3240
3600
400
min.
(m
3
/h)
-
-
-
-
-
504
576
720
864
1008
1152
1296
1440
[l/s]
-
-
-
-
-
140
160
200
240
280
320
360
400
max.
(m
3
/h)
-
-
-
-
-
6048
6912
8640
10368 12096 13824 15552 17280
[l/s]
-
-
-
-
-
1680
1920
2400
2880
3360
3840
4320
4800
500
min.
(m
3
/h)
-
-
-
-
-
-
-
900
1080
1260
1440
1620
1800
[l/s]
-
-
-
-
-
-
-
250
300
350
400
450
500
max.
(m
3
/h)
-
-
-
-
-
-
-
10800 12960 15120 17280 19440 21600
[l/s]
-
-
-
-
-
-
-
3000
3600
4200
4800
5400
6000
- this table specifies the complete measuring range of the
standard controller (volumetric flow range).
- If the customer absolutely wants a calibration curve different
from 12 m/s, it must be specified!
- When the air volume drops below the V
min
shown in the
chart, the correct functioning of the volumetric flow controller
is no longer guaranteed!
- If only one air volume is specified in the order (as V
max
value),
the volumetric flow controller will be delivered as variable vol-
umetric flow controller. The V
min
value will be set to the value
specified in the catalogue.
- If only one air volume is specified in the order (as V
min
or
V
konstant
value or without value specification), then the volu-
metric flow controller will be delivered as a constant volumet-
ric flow controller. The volume specified in the order is set to
the V
min
value, and the V
max
value is set to 100%.
- The air volumes can be changed using setting devices specif-
ic for the controller make, depending on the calibration curve
set ex works.
- For the parameter setting of the control components (all con-
trollers), an air density of 1.2 kg/m³ has been taken into ac-
count.
- Belimo compact controllers are height-compensated. They
are calibrated ex works to the system height in question of the
specified installation site.
- If no system height is given in the order, the controllers will
be calibrated to the altitude of the delivery address.
- If the customer does not specify whether the "Parallel" or
"Master/Slave" operating mode is desired, the controller is set
for the parallel operation (Master/Slave mode only upon cus-
tomer request).
- for alternative controller types, a V-min from 2 m/s can be set
(pneumatic controllers from 3 m/s)