Volumetric flow controller VAQS

®

08/23 - 8

Construction subject to change.

No return possible!

09.05.2019

Version:

Volumetric flow range for VAQS

®

When the air volume drops below the V

min

 shown in the chart,

the correct functioning of the volumetric flow controller is no
longer guaranteed!

Volumetric flow range

H

V

B

 (mm)

(mm)

100

150

200

250

300

350

400

500

600

700

800

900

1000

100

min.

(m

3

/h)

36

54

72

90

108

126

144

180

216

-

-

-

-

[l/s]

10

15

20

25

30

35

40

50

60

-

-

-

-

max.

(m

3

/h)

432

648

864

1080

1296

1512

1728

2160

2592

-

-

-

-

[l/s]

120

180

240

300

360

420

480

600

720

-

-

-

-

200

min.

(m

3

/h)

-

-

144

180

216

252

288

360

432

504

576

-

-

[l/s]

-

-

40

50

60

70

80

100

120

140

160

-

-

max.

(m

3

/h)

-

-

1728

2160

2592

3024

3456

4320

5184

6048

6912

-

-

[l/s]

-

-

480

600

720

840

960

1200

1440

1680

1920

-

-

300

min.

(m

3

/h)

-

-

-

-

324

378

432

540

648

756

864

972

1080

[l/s]

-

-

-

-

90

105

120

150

180

210

240

270

300

max.

(m

3

/h)

-

-

-

-

3888

4536

5184

6480

7776

9072 10368 11664 12960

[l/s]

-

-

-

-

1080

1260

1440

1800

2160

2520

2880

3240

3600

400

min.

(m

3

/h)

-

-

-

-

-

504

576

720

864

1008

1152

1296

1440

[l/s]

-

-

-

-

-

140

160

200

240

280

320

360

400

max.

(m

3

/h)

-

-

-

-

-

6048

6912

8640

10368 12096 13824 15552 17280

[l/s]

-

-

-

-

-

1680

1920

2400

2880

3360

3840

4320

4800

500

min.

(m

3

/h)

-

-

-

-

-

-

-

900

1080

1260

1440

1620

1800

[l/s]

-

-

-

-

-

-

-

250

300

350

400

450

500

max.

(m

3

/h)

-

-

-

-

-

-

-

10800 12960 15120 17280 19440 21600

[l/s]

-

-

-

-

-

-

-

3000

3600

4200

4800

5400

6000

- this  table  specifies  the  complete  measuring  range  of  the

standard controller (volumetric flow range).

- If the customer absolutely wants a calibration curve different

from 12 m/s, it must be specified!

- When  the  air  volume  drops  below  the  V

min

  shown  in  the

chart, the correct functioning of the volumetric flow controller
is no longer guaranteed!

- If only one air volume is specified in the order (as V

max

 value),

the volumetric flow controller will be delivered as variable vol-
umetric flow controller. The V

min

 value will be set to the value

specified in the catalogue. 

- If only  one air volume is  specified  in the  order  (as  V

min

  or

V

konstant

 value or without value specification), then the volu-

metric flow controller will be delivered as a constant volumet-
ric flow controller. The volume specified in the order is set to
the V

min

 value, and the V

max

 value is set to 100%.

- The air volumes can be changed using setting devices specif-

ic for the controller make, depending on the calibration curve
set ex works.

- For the parameter setting of the control components (all con-

trollers), an air density of 1.2 kg/m³ has been taken into ac-
count.

- Belimo compact controllers are height-compensated. They 

are calibrated ex works to the system height in question of the 
specified installation site.

- If no system height is given in the order, the controllers will 

be calibrated to the altitude of the delivery address.

- If the customer does not specify whether the "Parallel" or 

"Master/Slave" operating mode is desired, the controller is set 
for the parallel operation (Master/Slave mode only upon cus-
tomer request).

- for alternative controller types, a V-min from 2 m/s can be set

(pneumatic controllers from 3 m/s)

Содержание VAQS DS0 Series

Страница 1: ...Ferdinand Schad KG Steigstra e 25 27 D 78600 Kolbingen Telephone 49 0 74 63 980 0 Fax 49 0 74 63 980 200 info schako de www schako de Volumetric flow controller VAQS...

Страница 2: ...cessories 5 Technical data 7 Volumetric flow range 8 Technical data for Belimo components 9 Operating control Belimo components 9 Circuit diagrams 10 Setting the operating potentiometers calculation f...

Страница 3: ...mper axle support made of maintenance free plastic in factory presetting of the controllers The controllers have been calibrated and preset in factory this in factory presetting eliminates later setti...

Страница 4: ...f several connection pieces or pieces with fire dampers or silencers the larger minimum distances must be observed All volumetric flow controllers can be assembled with horizontal or vertical damper a...

Страница 5: ...51 Class 3 Housing leakage air flow to DIN EN 1751 class B with electric controller LMV NMV D3 MF not MP bus ca pable Control voltage 24 V AC 50 60 Hz Temperature compensation from 10 40 C Acoustic cl...

Страница 6: ...for VAQS with 1 baffle with 2 baffles with 3 baffles B mm KA K mm S mm De dB Okt fm Hz 63 125 250 500 1000 2000 4000 8000 150 1 100 50 2 6 16 26 48 48 33 15 200 1 100 100 1 3 9 18 36 37 22 13 250 1 1...

Страница 7: ...52 63 68 68 67 67 65 63 72 74 74 73 73 71 69 78 81 82 81 81 80 77 86 6 68 67 66 65 63 58 70 73 73 72 71 69 67 76 78 79 78 77 76 74 82 84 85 84 84 84 82 90 9 73 73 73 71 69 65 76 79 78 78 76 75 73 82...

Страница 8: ...tomer absolutely wants a calibration curve different from 12 m s it must be specified When the air volume drops below the Vmin shown in the chart the correct functioning of the volumetric flow control...

Страница 9: ...ve control CLOSED can be implemented via a diode see page 10 Operating control Belimo components Positive control damper CLOSED Energy saving in areas not in use by closing the supply and re turn air...

Страница 10: ...w Function 0 1 V 0 Damper CLOSED VAV control inac tive 0 2 2 V Vmin Vmin operating stage active 2 10 V Vmin Vmax Continuous opera tion Vmin Vmax No Designation Wire colour Function 1 black Feed AC DC...

Страница 11: ...viour S2 service function Adaptation Adaptation started by a Operating service unit b Key on the VAV Compact V1 VAV service VAV service active a Press both keys Adaptation Address simultaneously b VAV...

Страница 12: ...n of the Vnenn volumetric flow m h The calibration curve is usually 12 m s Upon customer request a smaller value can be selected Actual value measurement via feedback signal U5 using a voltmeter or PC...

Страница 13: ...ting range Vmin Vmax Vmin 0 100 of set Vnenn volumetric flow Vmax 30 100 of set Vnenn volumetric flow Command variable Y Input resistance min 100 k DC 2 10 V 4 20 mA with 500 input re sistance DC 0 10...

Страница 14: ...C DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be downloaded from the Be limo w...

Страница 15: ...tible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position indicator for diagnostics Display of t...

Страница 16: ...t personnel observ ing recognised technical rules and regulations 6 For polluted air the volumetric flow controllers must be used with an integrated controller with a static membrane pressure sensor I...

Страница 17: ...assembly Mode Volumetric flow Vmin Volumetricflow Vmax Acoustic cladding Damper position Example VAQS 0250 200 DD A007 0 00200 01500 DS2 NA VAQS Volumetric flow controller type VAQS rectangular desig...

Страница 18: ...m galvanised sheet steel with METU flange M2 Order details 01 Type 02 Width 03 Height 04 Material 05 Profile connection 01 02 03 04 05 Type Width Height Material Profile connection Example ZSQ 1000 04...

Страница 19: ...IN EN 1751 class B made of aluminium Meas uring rods made of aluminium blade support made of plastic With electric controller LMV NMV D3 MF control voltage 24 V AC 50 60 Hz requirement measuring air 0...

Отзывы: