5.3.1 Access to terminal box

• Unscrew the four screws of the plate 

cover (1).

• Remove, turn, and fixate the cover (2). 

Keep the terminal box attached to the 
plate cover.

6. Start-up

6.1 Approval (before start)

When the jet fans have been mounted 
and are serviceable their function, 
correct installation, and interaction must 
be established through an approval test.
The person responsible for the operation 
of the system must take initiative for this 
test
The approval test must be documented 
and kept by the person responsible for 
the operation of the system and must be 
presented on demand if it concerns jet 
fans approved for smoke control.
Before startup, check that the fans are 
clean and free from tools and foreign 

substances and that the impellers rotate 
freely.
Check also that the electrical connection 
complies with current regulations and 
that the wire guard of the inlet nozzles 
and the deflector in the outlet are 
installed properly.
The fan rotation direction is checked 
after a brief start. Refer to the arrow signs 
on the side of the fan.
Note, that during the first 30 minutes of 
operation the motor may consume more 
power than stated on the motor plate. 
Also, the amp consumption depends on 
the temperature.

6.2 Start procedure

Start procedure

1 Start  the  fan
2 Check for irregular sounds
3 Check after 30 minutes that the fan 

functions correctly.

7. Maintenance

The user must always keep the jet fans in 
good working order.
To ensure functionality and life of the 
fans the following must be observed.

7.1 Safety measures

Ensure that unintentional activation is 
impossible. Cut, for instance, the power 
in the fuse box or use another centrally 
placed power switch. Fans with 
automatic control may suddenly start 
unless the power supply is disconnected.

7.2 Maintenance of fans

7.2.1 CO fans

For fans used for CO ventilation yearly 
inspection and check of functionality is 
recommended.

7.2.2 Smoke control fans

Fans approved for smoke control and 
used for ventilation on a daily basis, 
must be inspected every six months.
Fans that are only used in case of fire 
must be inspected 4 times per year. 
It is important to comply with the motor 
supplier's guidelines for maintenance.

7.3 Cleaning

Clean the cabinet, outlet, motor, inlet and 
wire guard with a wet cloth. A vacuum 
cleaner fitted with a brush or pressurised 
air may also be useful, depending on the 
kind of filth that have settled on the fan 
unit.
The motor and inlet areas require the 
motor and fan wheel arrangement to be 
taken down and disassembled. Remove 
the motor to clean the inlet nozzle. It is 
recommended to leave the wire guard on 
the inlet nozzle, as it is riveted to the 
nozzle. See section “7.6 Disassembly of 
motor”.

See section “7.7 Assembly of motor” for 
reassembly instructions.

7.4 Vibrations 

The fan is factory-balanced to minimise 
vibrations during operation. If 
vibrations occur it normally indicates 
accumulation of dust and dirt on the 
rotor system. If the problem remains 
after ordinary cleaning, please contact 
professional assistance. Continuous 
operation with vibrations may damage 
both motor bearings and impeller.
Check the vibration dampers in the 
suspension brackets for ruptures and 
replace the dampers at signs of ruptures.

7.5 Motor

The motor has closed bearings that 
should be changed in accordance with 
the motor supplier's recommendations.

7.6 Disassembly of motor

Before start, follow the procedure in 
section “7.1 Safety measures”.
Novenco recommends the use of a lift 
and that only the motor arrangement is 
taken down and instead of the entire fan 
unit.

Procedure for dismounting

1 Loosen the external motor cable 

connector.

2 Remove the terminal box cover plate 

and take out the terminal box. Turn 
and affix the cover with a single screw 

Figure 6.

Access to terminal box

Important:

The fan is designed for 
continuous operation. 
The following kinds of 
operation may cause 
fatigue break in the 
impeller and endanger 
people.

Operation in stall area - 
Operation with 
pulsating counter 
pressure - called pump 
mode

Operation with 
repeated starting and 
stopping

Uneven flow velocity 
through fan

If in doubt Novenco 

should be contacted to 
assess fan suitability.

1

2

Important:

Shut off and disconnect 
the fan power supply 
before beginning any 
work or cleaning on the 
fans.

Important:

Do not use high-pressure 
water cleaning.