background image

2

4. Storage

Jet fans are vulnerable if stored outdoors.
At indoor storage with good ventilation 
and no risk of condensation the storage 
period is 6 months.
The storage location must be free from 
vibrations, as these can damage the 
motor bearings.
At storage longer than 3 months the fan 
wheels must be turned (moved) 
regularly. 
During subsequent mounting the fans 
must be inspected for damages and 
corrosion. Ensure that the motors do not 
contain condensation before start up.

5. Installation

5.1 Before installation

Unpack the jet fan by removing the top 
and sides of the box. Leave the fan on the 
support on which it rests.
Check that the impeller can rotate freely 
in the fan casing.
Mount the enclosed suspension brackets 
on either side of the fan casing. Tighten 
them with a torque of at least 23 Nm.

5.2 Installation

The jet fans must be installed with an 
open inlet area below the fans. The outlet 
side must have a minimum of 2 m 
obstruction free clearance. Obstructions 

include beams, columns, and other large 
objects that affect the airflow.
The fans are fitted with arrow signs 
indicating the direction of airflow and 
rotation.

The suspension brackets are 
dimensioned to leave a minimum of 
5 mm space between the ceiling and the 
top of the fan casing. The brackets must 
be the only contact points with the 
ceiling and the 5 mm space must be 
available across the entire surface. This is 
to ensure the dampers work properly.

If jet fans are mounted within the fire cell 
(the fire room) they must only be 
installed on non-flammable ceilings/
materials and must comply with current 
national regulations. Jet fans should in 
general be installed so that there is no 
risk of them falling down in the event of 
fire.
Expansion bolts without approval for 
high temperature must be of steel, be 
minimum M10, and must be installed 
twice as deep as required by the 
approval (at least 60 mm). The static load 
must not exceed a pull of 500 N.
Expansion bolts with documented load 
capacity during fire must be installed 
and loaded as stated in the approval.

Mount the jet fan to a horizontal plane 
with a natural frequency at least 20% 
from the fan rotation speed.
After final fastening of the fan check that 
the impeller rotates freely in the fan 
casing.
To ensure performance and sound level 
the airflow must be unobstructed.

5.3 Electrical connection

The fan power cable must be wired in 
compliance with current rules and 
legislation.
The connection must also be performed 
in compliance with current rules and 
legislation and by authorised staff. The 
fan is connected through the motor 
protection switch based on the nominal 
motor current. The connection must be 
made directly in the terminal box 
mounted internally below the plate 
cover.
Emergency stops must be installed in 
compliance with current rules and 
legislation.
For connection, see fig. 4 and 5.

Figure 3.

Mount suspension brackets

A

23 Nm

Figure 4.

Circuit diagram in motor 
terminal box

Figure 5.

Connections in terminal box

Tw

o speed

(Dahlander)

Max. r/min

Min. r/min

Low speed

High speed

Earth

L1 L2 L3

L1 L2 L3

A [mm]

B [mm]

C [mm]

D [mm]

E [mm]

F [mm]

G [mm]

CGF 500

1296.5

900

265

73.5

27

850

790

Figure 2.

Dimensions

A

D

E

F

G

B

C

Отзывы: