background image

Page 

2

UK

Introduction

 

The KEY-K01, KEY-KP01 and KEY-KPZ01 are wired 
keypads for use with i-on intrusion systems.
Features:

 

Allows installers to access the Installer menu, 
and users to set/unset the system or access 
the User menu.

 

Built-in proximity reader, and terminals for an 
external KEY-EP proximity reader (KEY-KP01 
and KEY-KPZ01 only).

 

Two zones and a programmable output (KEY-
KPZ01 only).

 

Backlit display and keys.

 

Navigation key for menus, with built-in alert 
LEDs.

 

Configurable A, B, C, D keys for setting, 
unsetting or operating outputs, with built-in 
LEDs to show set state.

 

Cover and back tamper detection.

Step 1: Choose the mounting 

location

 

Locate the keypad out of sight of potential 
intruders and within the area protected by the 
intrusion system.

 

Choose a convenient location and height 
for users.

 

Check that the maximum cable lengths 
will not be exceeded (see the control unit’s

 

Installation Manual

).

 

Make sure that a KEY-KP01 or KEY-KPZ01 is 
not closer than 1 metre to another proximity 
reader, or located behind a door, coat rack or 
other covering.

Step 2: Mount the backplate

1. Using a thumb (not a tool), flip down the 

screw covers and remove the screws (Figure 
2).

2. Lift the cover upwards, off its hinges.
3. Mount the backplate to the wall (Figure 3).

Step 3: Configure the links

ADDR 2-4 − If you are using a legacy i-on16 
or i-on40*, each keypad must have a separate 
address. Leave all links off for address 1, or fit 
the appropriate link for address 2, 3 or 4. For 
other control units, leave all ADDR links off.
*Please do not confuse the i-on40 with the 
modern i-on40H.
BRIGHT − If you are using a legacy i-on16 or 
i-on40*, fit the link to enable full brightness 
for the backlight, or remove the link for normal 
brightness. For other control units, leave the 
link off (brightness can be controlled from the 
Installer or local menu).
TERM − Fit the link if the keypad is at one end 
of the bus. RS485 termination can improve 
performance in electrically noisy environments.

Step 4: Connect all wiring

Connect all wiring to the PCB (Figure 4). 
The bus connections are the only mandatory 
connections to the keypad. Note: 

 

Before you install any wiring, disconnect 
all power to the control unit, including the 
battery.

 

In general, the keypad requires 7/0.2 
unscreened alarm cable. Screened cable may 
be needed if the site has high levels of radio 
interference.

 

Keep the keypad cable separate from any 
other wiring such as mains supply cables, 
telephone cables, computer network cables, 
R.F. cables, and cables supplying sounders or 
extension loudspeakers.

 

For full details of wiring requirements, please 
refer to the control unit’s 

Installation Manual

.

External proximity reader

Please refer to the KEY-EP instructions for 
details of how to install a KEY-EP. Also enable EP 
Tamper
 (see 

Using the local menu).

Output

The default polarity for the OP terminal is 0V 
when active, and 12Vdc when inactive. You 
can invert the polarity using the 

Wired Outputs 

option in the Installer menu.

Zones

To use the keypad zones, you must enable them 
using the keypad’s 

Edit Keypad option in the 

Installer menu.
Fully-Supervised Loop (FSL), 4-wire CC and 
2-wire CC zone connections are supported.
If you require details of how to wire zones, 
please refer to the control unit’s 

Installation 

Manual

.

The zone number the control unit allocates to 
each zone is dependent on the type of control 
unit you are using and whether expanders 
are already configured. For details of zone 
numbering, please refer to the control unit’s 

Installation Manual.

Step 5: Attach the front cover

Attach the front cover of the keypad, and secure 
it with the two screws. 

Step 6: Address and configure the 

keypad

Use the 

Wired Keypads option in the Installer 

menu to:

 

Set the address. Select Address Bus Device in 
the Installer menu, then press and hold A and 

 together. (For legacy panels, see “Step 3: 

Configure the links”.)
Note: You can delete the keypad’s address 
by pressing D and 

 together while the cover 

is open.

 

Select partitions (if applicable).

 

Configure the A, B, C, D keys (optional).
Note: You can enable the A, B, C, D LEDs 
using the local menu (see “Using the local 
menu”).

 

Enable the keypad zones and external 
proximity reader (if applicable).

 

Change settings such as the backlight 
brightness and wired zone type (as required). 

Optionally, you may want to adjust the tone 
volume or set local options, as described next.

Adjusting tone volume

You can use the volume control shown in Figure 
4 to adjust the volume of non-alarm tones (such 
as the entry/exit tone). The volume of alarm 
tones is fixed. 
Before opening the keypad, enter the Installer 
menu (to avoid an alarm), then turn the control 
clockwise to increase volume, or anticlockwise 
to reduce volume.

Using the local menu

The keypad has a local menu, which has a 
number of settings that are specific to the 
keypad you are using. To access the menu:
1. Display the Installer menu.
2. Remove the front cover of the keypad (if it is 

not already removed) to activate the tamper 
switch.

3. Press and hold B and 

 for two seconds. You 

will see the following.

MENU

 ABCD LEDs        

x

4. Press 

u

 or 

n

 to select the required option 

(do not press 

).

5. Press 

 or 

 to change the setting (on the 

display, a cross means disabled, and a tick 
means enabled).

6. Press 

 to save changes or 

 to cancel 

changes.

The following options are available:

ABCD LEDs

This option enables or disables the LEDs behind 
the ABCD keys. The LEDs show the set status 
of the system (for example, setting part-set A 
illuminates the LED behind key A).

Backlight

This option enables or disables the local 
backlight setting. Enabling the backlight at the 
keypad overrides the keypad backlight setting 
in the Installer menu and results in permanent 
illumination of the backlight at normal 
brightness.
Disabling the backlight at the keypad allows 
the settings in the Installer menu to specify 
the backlight mode (on, off or timed) and 
brightness.

Status OK LED

This option relates to the green “OK” LED 
located behind the navigation keys.  When 
enabled, it causes the LED to illuminate steadily 
when there is no uncleared fault or alarm 
condition present.
If you disable Status OK LED, the LED does not 
illuminate while the keypad backlight is off. As 
soon as a key is pressed (which switches on the 
backlight), the green LED will illuminate if there 
is no uncleared fault or alarm.
The option may be of use if, for example, the 
keypad is installed in a bedroom and the user 
requires the keypad to remain dark.

Status FLT LED

This option relates to the red fault LED located 
behind the navigation keys. When enabled, 
it causes the LED to illuminate steadily when 
there is an uncleared fault or alarm that the 
control unit has reported, such as a mains fail 
or a tamper. The red LED continues to be lit until 
the fault or alarm is cleared.
If you disable Status FLT LED, the LED does not 
illuminate while the keypad backlight is off. As 
soon as a key is pressed (which switches on the 
backlight), the red LED will illuminate if there is 
an uncleared fault or alarm. 
The option may be of use if, for example, 
the keypad is installed in a bedroom and 
the user requires the keypad to remain dark 
(for example, to prevent the LED from being 
continually lit until an engineer clears an alarm).
Note: This option controls the red LED only 
for faults and alarms that the control unit has 
reported to the keypad. The following faults are 
detected by the keypad, and therefore always 
illuminate the red LED, irrespective of the 
setting of Status FLT LED:

 

No address (expandable systems only) — 
slow flash of red fault LED.

 

Communications problem — fast flash of red 
fault LED.

EP Tamper (KEY-KP01/KEY-KPZ01)

Enable this option if a KEY-EP external proximity 
reader is connected. When enabled, the keypad 
polls the KEY-EP at intervals and reports a 
tamper event if the KEY-EP does not respond.

Maintenance

The only maintenance required is cleaning 
and an annual test of the keypad using the Test 
menu at the control unit.
Clean the outside of the case using a soft 
dry cloth. Do not use water, solvents or  any 
proprietary cleaning agents.

Specifications

Supply Voltage: 12Vdc.
Current Consumption (max):

 

KEY-K01: 58mA in alarm with backlight bright. 
18mA quiescent with backlight off.

 

KEY-KP01: 60mA with internal proximity 
reader on, and backlight bright (no external 

Содержание KEY-K01

Страница 1: ...e 4 mm x 25 mm No 8 Minimo 3 viti svasate di 4 mm x 25 mm N 8 Minimaal 3 van 4 mm x 25 mm Nr 8 verzonken schroeven Figure 3 Mounting the backplate Abb 3 Die Rückplatte montieren Figure 3 Montage de la plaque arrière Figura 3 Montaggio della piastra posteriore Afbeelding 3 Grondplaat monteren DE Installationsanweisungen IT Istruzioni per l installazione Figure 4 Keypad PCB Abb Keypad Leiterplatte F...

Страница 2: ...ote You can enable the A B C D LEDs using the local menu see Using the local menu Enable the keypad zones and external proximity reader if applicable Change settings such as the backlight brightness and wired zone type as required Optionally you may want to adjust the tone volume or set local options as described next Adjusting tone volume You can use the volume control shown in Figure 4 to adjust...

Страница 3: ... ENTIRE OBLIGATION OF EATON THE CONTENTS OFTHIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEENTHE PARTIES In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or other wise for any special indirect incidental or consequential damage or loss whatsoever including but not limited to damage or loss of use of equipmen...

Страница 4: ...eibungen und Sicherheitshinweise im vorliegenden Dokument basieren auf den Erfahrungswerten und der Beurteilung der Eaton Corporation Eaton und decken möglicherweise nicht alle Eventualitäten ab Sollten darüberhinausgehende Informationen benötigt werden stehen Mitarbeiter des Vertriebsbüros von Eaton gern zur Verfügung Der Verkauf des in diesem Dokument beschriebenen Produkts unterliegt den in den...

Страница 5: ... annule le réglage de rétroéclairage du clavier défini dans le menu d installation et permet d obtenir un éclairage permanent du rétroéclairage avec une luminosité normale La désactivation du rétroéclairage du clavier permet de spécifier le mode de rétroéclairage allumé éteint ou temporisé et la luminosité dans le menu d installation Status OK LED LED d état OK Cette option concerne la LED OK vert...

Страница 6: ...RS485 può migliorare le prestazioni in ambienti elettricamente rumorosi Passo 4 Collegamento del cablaggio Collegare tutti i cavi al PCB Figura 4 I collegamenti del bus sono gli unici collegamenti alla tastiera obbligatori Nota Prima di installare il cablaggio scollegare l alimentazione elettrica dall unità di controllo compresa la batteria In generale la tastiera richiede un cavo di allarme non s...

Страница 7: ... LE PARTI Eaton non sarà in alcun caso responsabile nei confronti dell acquirente o dell utente in base a contratto atto illecito negligenza compresa responsabilità oggettiva o altro per nessun tipo di danno o perdita speciale indiretto incidentale o conseguente tra cui a titolo esemplificativo danni o perdite di utilizzo dell attrezzatura dell impianto o del sistema di alimentazione spese di inve...

Страница 8: ...ED op als er een onopgeloste fout of alarmtoestand is Deze optie kan bijvoorbeeld nuttig zijn als het toetsenbord in een slaapkamer is gemonteerd en de gebruiker wenst dat het onverlicht blijft bijv om te verhinderen dat de LED continu aanblijft totdat een monteur komt om het alarm op te heffen Opmerking Via deze optie stelt u de rode LED alleen in voor fouten en alarmen die het controlepaneel aan...

Отзывы: