5.2 ROUTINE MAINTENANCE
Routine maintenance is necessary in order to guarantee proper operation and preservation of the degree of protection of the
switch - disconnector in enclosure.
1) Check that the gasket is intact each time the enclosure is opened.
2) Check that the closing screws are all in position and well-tightened each time the enclosure is closed.
3) Check that the screws/bolts fastening the enclosure to the wall are well-tightened and free of corrosion each year.
4) Check the seal of the cable glands each year.
5) Check for any damage to the enclosure each year.
6) Check that the screw terminals are tightened as indicated in table 2.
7) In environments with the presence of combustible dust, the outer surface of the enclosure must be cleaned periodically,
preventing the deposited dust from reaching a thickness of more than 5 mm.
5.3 CHEMICAL AGGRESSION
The ISOLATORS-EX device has been manufactured using:
• Thermoplastic alloy (PC Xiloxane) for the enclosure base and cover; switch facing and rotary switch.
• Thermoplastic rubber for the base-cover gasket and knob gasket.
• Screws in AISI316 stainless steel.
The environment in which the device will be installed must be considered carefully in order to verify the compatibility of these
materials with the presence of chemical agents or corrosive atmospheres.
5.4 DISPOSAL
The product must be disposed of in compliance with national rules on the disposal and recycling of industrial waste.