ISOLATORS-EX
MP36511
ZP90828-5
11
EN
An example of the label used for the SWITCH - DISCONNECTOR is shown below:
TÜV IT 14 ATEX 005
Ex tb IIIC T90°C Db Ta -25°C to + 60°C
Ex tb IIIC T80°C Db Ta -25°C to + 40°C
0051
II 2D
590.XGE2002
DO NOT OPEN WHEN ENERGIZED IN PRESENCE OF EXPLOSIVE ATMOSPHERE
Via Costa Erta 15 Parre BG ITALY
Year 2014
IP66
IP66
TÜV IT 14 ATEX 005
Ex tb IIIC T90°C Db Ta -25°C to + 60°C
Ex tb IIIC T80°C Db Ta -25°C to + 40°C
0051
II 2D
590.XGE3202
WARNING:THE CABLE ENTRY POINT MAY EXCEED 95°C
DO NOT OPEN WHEN ENERGIZED IN PRESENCE OF EXPLOSIVE ATMOSPHERE
Year 2014
Via Costa Erta 15 Parre BG ITALY
IP66
IP66
590.XGE2002: switch-disconnector in enclosure.
590.XGE3202: 32A switch-disconnector in enclosure.
Detail of the product traceability on the adhesive label.
Year
0051
2014
II 2D
S/N
Cod.
xxxxxxxxx
590.XGE2002
Via Costa Erta 15 Parre BG Italy
TÜV IT 14 ATEX 005
THIS DOCUMENT MUST BE READ CAREFULLY BEFORE INSTALLATION
These instructions are intended for
: expert electricians or appropriately trained personnel.
1. SAFETY INFORMATION
The switch - disconnectors in enclosures of the ISOLATORS-EX Series can be used for fixed installations in environments with a
potential risk of explosion, due to the presence of combustible dust, classified as zone 21 and zone 22.
These instructions for installation, use and maintenance must be kept in a safe location for future reference. During operation or
maintenance work on the apparatus, do not leave this manual or other objects inside the enclosure. Use the ISOLATORS-EX Series
switch - disconnectors in enclosures for their approved use only, and keep them completely intact and clean.
The switch - disconnectors in enclosures are designed to withstand shocks of 7 J and to be used under normal vibration conditions.
They are not designed for use in environments subject to extreme vibrations.
The enclosure is made of thermoplastic material. The type of protection cannot be guaranteed if the product is installed incorrectly.
Use only original spare parts supplied by SCAME. No modification/work is permitted on the switch - disconnector in enclosure
unless specifically indicated in this manual.
DO NOT OPEN THE ENERGISED ENCLOSURE IN PRESENCE OF AN EXPLOSIVE ATMOSPHERE
Always follow the national safety rules and the safety instructions contained in this manual when ever working on the device.
2. COMPLIANCE WITH STANDARDS
The switch – disconnectors in enclosure of series
XGE
and
XEM
are intended for use in Zone 21 and 22, in compliance with the
provisions of Directive 2014/34/EU:
Содержание 590.XEM200X
Страница 45: ...ISOLATORS EX MP36511 ZP90828 5 45 BG 1 46 2 46 3 47 4 48 5 49 mm...
Страница 66: ...ISOLATORS EX MP36511 ZP90828 5 66...
Страница 67: ...ISOLATORS EX MP36511 ZP90828 5 67...
Страница 68: ...SCAME PARRE S p A VIA COSTA ERTA 15 24020 PARRE BG ITALY TEL 39 035 705000 FAX 39 035 703122...