16 ASCII PROTOCOL SUPPORT
The EtherMeter is available with RAW-ASCII protocol support (Optional. ASCII-Version Only).
Many PLC’s and RTU’s are equipped with extra serial ports that are capable of collecting data from
raw ASCII terminal devices such as bar code readers. For compatibility with these PLC’s, the
EtherMeter
provides a “Raw ASCII Protocol” output.
When the EtherMeter is set to
“Raw ASCII” mode (available via the Setup Menu), the following data
is transmitted from the active serial port every three (3) seconds:
: <TOTAL1> ; <TOTAL2> ; <FLOW1> ; <FLOW2> ; <ROLLOVERS1> ; <ROLLOVERS2> ;
<METER_FAULT1> ;<METER_FAULT2> ; <ANALOG_IN1> ; <ANALOG_IN2> ;
<AUX_DIGITAL_IO_1> ; <AUX_DIGITAL_IO_2> ; <AUX_DIGITAL_IO_3> <CR> <LF>
Each transmission is preceded by a ‘:’ delimiter, and ended with a <CR><LF> delimiter. There are
no spaces or carriage returns between the data fields, as each
field is separated by a ‘;’ delimiter.
TOTALIZATION AND FLOW DATA FORMAT:
The EtherMeter was designed in such a way as to simplify and compress the formatting of all
reported data. In order to achieve this level of simplicity, the scale factors (EXP1 and EXP2) have
been stripped from the reported totals (Note: the 2x16 LCD display and web page provide scaled
displays).
For example, consider the following case of an 8-digit register plus two (2) fixed zeros on the right
(EXPn=+2):
R
G
B
1 2 3 4 5 6 7 8
0 0
9
GALLONS
,
,
,
In this case, the actual total is 1,234,567,800 gallons. However, the ASCII protocol will report the
total as: 12345678. If scaling to GALLONS is desired, then the reading device must perform the
scaling (multiply by 100).
Regarding flow, all reported flow rates are multiplied by 1000 to eliminate the need for floating point
formatting. In this case, if the actual flow rate is 987.6 GPM, then the ASCII protocol will report the
flow as 987600 (MilliGallons Per Minute). If scaling to GPM is desired, then the reading device
must perform the scaling (divide by 1000). Also, keep in mind that all reported ASCII data is
formatted in decimal.
Содержание EtherMeter EM-100
Страница 2: ......
Страница 38: ...36 Setup Screen 2 of 8 Serial Port Setup Setup Screen 3 of 8 Networking Setup...
Страница 39: ...37 Setup Screen 4 of 8 Auxiliary I O Setup Setup Screen 5 of 8 Interface Setup...
Страница 41: ...39 Setup Screen 8 of 8 Meter Read Diagnostics...
Страница 79: ...This Page Intentionally Blank...