DIP SWITCH DEFINITIONS:
#1
#2
#3
#4
#5
#6
#7
#8
UP
RS-232C
SERIAL
PORT ACTIVE
(RS-485 SERIAL
PORT INACTIVE)
UP
RS-485
SERIAL
PORT ACTIVE
(RS-232C SERIAL
PORT INACTIVE)
UP
120 OHM
TERMINATION
RESISTOR
ACTIVE
(RS-485 ONLY)
RESERVED
-N/C-
RESERVED
-N/C-
RESERVED
-N/C-
UP
BACKLIGHT AND
POWER-LED ON
UP
SETUP MODE
MODBUS/SERIAL
DF1/SERIAL
INACTIVE
DOWN
RS-485 SERIAL
PORT IN-ACTIVE
RS-232C SERIAL
PORT ACTIVE
DOWN
RS-232C SERIAL
PORT INACTIVE
(RS-485 SERIAL
PORT ACTIVE)
DOWN
120 OHM
TERMINATION
RESISTOR
INACTIVE.
(RS-485 ONLY)
DOWN
BACKLIGHT AND
POWER-LED OFF
(POWER SAVING
MODE)
DOWN
RUN MODE
Figure 4B. DIP Switch Definitions
FACTORY-RESET BUTTON:
The FACTORY RESET Button is located to the right of the dip switches. When the FACTORY
RESET button is depressed during a power cycle (or soft reboot), then all user-settings are
discarded, and the factory default settings are restored.