Hardware manual PCD7.LRxx-PG5 room controller │ Document 27-653; version ENG07 │ 2019-03-21
Saia-Burgess Controls AG
Introduction
General guidance
2-13
2
2.8.4
System compatibility
The following versions are recommended for optimal FBox library use with PG5:
●
PG5
>= V2.3.113
●
Firmware PCD7.LRxx-xx (IRM)
>= 1.1.0.07
●
Firmware PCD (PCD plus system) >= 1.26.xx
●
Firmware PCD (PCD system)
>= 1.24.67
●
Firmware remote IO (L series)
>= 1.04.xx
●
Firmware remote IO (S series)
>= 1.08.xx
2.8.5
Addressing the room controllers
We recommend setting the S-Bus address (or Modbus address) for the room con-
trollers before installation with PG5 via the Micro-USB port, then writing down the
S-Bus address (or Modbus address) on a separate sticker to be affixed or attached
to the room controller or building floor plan.
This has the advantage that after installation, the room controller can be com-
missioned and the application program can be downloaded (along with any FW
updates) via the RS-485 bus, making it unnecessary to configure each room con
-
troller directly in situ.
2.8.6
Media Backup/Restore
Description
This FBox must be used on a program-
mable IRM whenever an FBox from the
library [programmable IRM] is used, and
it must also be used to “Media Backup/
Restore” adjustment parameters for
any FBoxes from other libraries or us-
er-defined symbols that should also be
backed up/restored automatically.
Functional
No media on programmable IRM are battery-protected; they are all volatile. The
adjustment parameters are initialised with the default settings after download,
but may be changed during operation by the user. Those values will be lost if the
power is switched off and on, after which the device will reset to the default values.
This FBox is required to backup and restore values modified during operation. A
backup/restore mechanism for a maximum 1000 elements in total (only registers
or flags) has been introduced. PG5 automatically detects adjustment parameters