Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Hardware
1-3
1
Technical Data
1.2
Technical Data
Technical specification
All specifications at 25°C ambient temperature, unless otherwise noted.
Sensor types
TC Type J
TC Type K
Pt100
Pt1000
Ni100
Ni1000
Input range for tempera-
ture sensors
-210…1200°C¹
DIN IEC 584
-270…1372°C¹
DIN IEC 584
-200…850°C
DIN IEC 751
-60…250°C
DIN IEC 43760
Measurement range
-75 mV…+75 mV
Pt/Ni100: 0…600 Ω
Pt/Ni1000: 0…5000 Ω
Resolution
0.1°C
0.1°C
2.5 μV
0.01 Ω (600 Ω range)
0.10 Ω (5000 Ω range)
Measuring error in % of
full scale value²
0.05 %
0.05 %
Measuring error
in °C
Alternative to the “measuring error in %” specification above:
-100…+100°C: <0.4°C
-150…+500°C: <0.7°C
-150…+1000°C: <1.0°C
-100…+100°C: <0.3°C
-150…+500°C: <0.4°C
-200…+850°C: <0.5°C
Temperature coefficient
of full scale value²
10 ppm/K
80 ppm/K
Sampling time
per channel
250 ms
Measurement resolution
16 bit
50Hz rejection
60Hz rejection
> 75 dB
> 60 dB
Line break detection
Short circuit detection
x
x
Linearization
on Board
Compensation of cold
junction temperature
on Board
N/A
Cold junction internal
Yes³
N/A
Cold junction external
Yes
N/A
Connection techniques
for resistors (RTD’s)
N/A
2-wire
3-wire
4-wire
Galvanic isolation
500 VDC between Saia PCD
®
and analogue inputs
¹) For thermocouples, the full measurement range is offered. The specifications of resolution and accu
-
racy are given for temperatures higher than -150°C. For lower temperatures than -150°C, the char
-
acteristics of thermocouples become worse. If thermocouples are used in this very low temperature
range, the tolerance should be calculated using the tolerance specifications for the ±75 mV range and
the thermocouple characteristic.
²) Measuring error in % and temperature coefficient specifications made for the measurement ranges
±75 mV, 600 Ω, 5000 Ω.
³) Technical data of the internal cold junction are specified in the following section.