Saia-Burgess Controls AG
Manual for PCD2.W745 and PCD3.W745
│
Document 26-796 E
NG06 │ 2018-10-12
Programming
Programming with PCD Classic
3
3-4
3.1.2 Programming with FBs
To use the PCDx.W745 in Saia PCD
®
Classic systems, FBs are delivered in the
Saia PG5
®
package.
FB Init
The Init FB has the following parameter structure:
FB Init
Parameter
Type
Description
K 1…16
[K] input
module Number according to file D2W745_B.mba
TC_K*
[K] input
Sensor type CH0
CJCint*
[K] input
Configuration / connection CH0
TC_K*
[K] input
Sensor type CH1
CJCint*
[K] input
Configuration / connection CH1
TC_K*
[K] input
Sensor type CH2
CJCint*
[K] input
Configuration / connection CH2
TC_K*
[K] input
Sensor type CH3
CJCint*
[K] input
Configuration / connection CH3
Celsius*
[K] input
Measurement unit
InitError
[F] output Initialization error indicator
WrongConfig
[F] output
No or wrong configuration indicator
NoCalibration [F] output Internal module calibration check
*
See table below for predefined configuration codes.
Predefined configuration codes for the supported temperature sensors:
Configuration / Connection
CJCint
CJCext
R2wire
R3wire
R4wire Voltage NotUsed
Input range
TC_K
TC_J
Pt100
Ni100
Pt1000
Ni1000
U75mV
R600
R5000
NotUsed
●
When CJCext is configured, the temperature of the external reference junction
is measured using channel 0. Therefore, channel 0 can’t be configured for
CJCext.
●
If a wrong configuration is sent to the module, the NoConfig indicator becomes
high and the module does not go in data acquisition mode.
Predefined configuration codesfor the measurement unit:
Celsius
Temperature value in 1/10°C
The module converts the measured value
in the selected measurement unit.
Fahrenheit
Temperature value in 1/10°F
Kelvin
Temperature value in 1/10 K