background image

Battery Replacement

• Switch off the electricity at the mains, both switched and permanent supply.
• Allow batteries to fully discharge then reconnect to supply and allow to
   charge for 24 hours.
• Test again for 3 hours, if light does not remain lit change the battery pack
    as follows:
    - Disconnect from the mains supply both permanent and switched supply.
    - Undo two screws at the end of the product then pushing the two quick
      release tabs on the one side of the front cover to separate the front cover,
      diffuser from product. Keep screws in safe place for refitting later.
    - Undo the two screws holding the gear tray and fold down.
    - Unplug the battery lead from the lead coming from the PCB. Remove any
      cable ties around the cables.
    - Remove the battery pack and lift the battery pack out of the fitting. Waste
      electrical products should not be disposed of with household waste. Please
      recycle where facilities exist. Check with your local authority or retailer for
      recycling advice.
    - 

Replace the battery with a LiFePO4 3.2V 1500mAh only

. Use of a

      different type of battery will damage the product.
    - Write current date on the new battery pack.
    - Fit new battery pack in position and re-secure using the screws set aside
      earlier. Refit the cable ties in position and then plug battery pack into the
      PCB.
    - Plug battery pack into circuit board.
    - Close and secure gear tray and replace diffuser.
    - Restore power and allow to charge for 24 hours.
    - Perform full operation check and update test record.  

If after routine operation check, the lamp does not remain lit for the three
hour period, a new battery pack may be required.

Live Voltages may be present in this unit even when turned off or when completely disconnected. 

We recommend cleaning with a soft dry cloth. Do not use

solvents or abrasive cleaners as these could damage the finish. For your safety, always switch off the power supply before cleaning.

This bulb is protected by a shade. This part must be replaced immediately should the shade become cracked or damaged. This fitting must
not be used without the shade in place. 

Replace Cracked Shade

Self-Test Function

This product has self testing function. Visual inspection of
the battery charge LED as below:

www.saxbylighting.com

Instruction manual

97817

Sight Plus Self Test

Care and Safety

Wiring

• This product is double insulated and must not be earthed. If there are any incoming

    earth cables, they must be joined together and well insulated with good quality

    insulation tape. This is to ensure earth continuity throughout your property.
• Having correctly identified the wiring from your existing light fitting, connect to the

   quick fit connection block in the following way, using the supplied link cables

   where necessary.

LIGHT FITTING

SUPPLY

INSERT CABLE

PUSH DOWN

Check that...

•  You have correctly identified the wires.
•  The connections are tight.

PL

SL

N

LINK CABLE

Maintained (Unswitched) Wiring:

The product is on permanently and comes on during a power failure.

PERMANENT LIVE

NEUTRAL

BLUE(N)

BLACK(L)

BROWN(L)

LIGHT FITTING

SUPPLY

Non-Maintained Wiring:  

The product is normally off and comes on during a power failure.

PL

SL

N

PERMANENT LIVE

NEUTRAL

BLUE(N)

BLACK(L)

BROWN(L)

LIGHT FITTING

SUPPLY

Maintained (Switched) Wiring: 

The product is used as a normal light - switch on/off, light turns on/off.

comes on during a power failure.

PL

SL

N

PERMANENT LIVE

NEUTRAL

BLUE(N)

BLACK(L)

BROWN(L)

SWITCH LIVE

LIGHT FITTING

SUPPLY

Automatic Monthly (Every 30 Days): 

(in addition to the daily check)

The results of the short duration test shall be recorded.

Automatic Annually (Every 180 & 360 Days): 

(in addition to the daily check)

The results of the full duration tests shall be recorded.

Manual Testing - 

Can only be completed under mains conditions

Manual Simulated Power Failure
Manual 30 Day Test
Manual 180/360 Day Test
Manual Fast Test (24 minutes)

Hold test button until you hear 1 beep
Hold test button until you hear 2 beeps
Hold test button until you hear 3 beeps
Hold test button until you hear 4 beeps

Abort Test

Hold the test button for 15 seconds, when you

hear the long sound, the self-test function will

restore the defaults

Fault Indicators:

Red LED flashing once a second, Green LED off,

Beeps twice every minute until fault rectified
Red LED flashing twice a second, Green LED off,

Beeps twice every minute until fault rectified

Battery/Charging Fault

Lamp Fault

Failed Duration Test

Red LED solid, Green LED off, Beeps twice every

minute until fault rectified

Performance Indicators:

Normal Operation

Automatic 30 Day Test
Automatic 180/360 Day Test

Manual Simulated Power Failure
Manual 30 Day Test
Manual 180/360 Day Test
Manual Fast Test (24 minutes)

Red LED off, Green LED Solid
Red LED off, Green LED flashing once a second
Red LED off, Green LED flashing twice a second
Red LED off, Green LED off

Red LED off, Green LED four times a second

Red LED off, Green LED flashing once a second
Red LED off, Green LED flashing twice a second

•  No loose strands have been left
    out of the connection block.

V1 21/07/2021

EU Manufacturer: 1 Gnarrenburg, 27442

UK Manufacturer: BH17 7BY

Отзывы: