Savant Power System Deployment Guide - Sol-Ark
Copyright 2022 Savant Systems, Inc
009-2222-01 | 121222
- 26 -
Timer Settings
Feature
Timer
Savant Setting
Adjustment Range
Display Screen
1C
override momentary
Normal source outages
1
0 to 6 sec
see NOTICE below
N Fail (1C)
1F
override momentary
Emergency source
outages
1
0 to 6 sec
see NOTICE below
E Fail (1F)
2B
transfer to Emergency
(if Normal fails)
0
0 to 60 min 59 sec
N to E N Fail (2B)
transfer to Emergency
(if just a test)
0:05
0 to 60 min 59 sec
N to E Test (2B)
2E
engine cooldown
5 minutes
0 to 60 min 59 sec
Cool Down (2E)
3A
Retransfer to Normal
(if Normal fails)
30 minutes
0 to 60 min 59 sec
E to N N Fail (3A)
Retransfer to Normal
(if just a test)
30 seconds
0 to 9 hours
59 min 59 sec
E to N Test (3A)
31F
Normal to Emergency
pre-transfer signal
0
0 to 5 min 59 sec
N to E PreX (31F)
31G
Emergency to Normal
pre-transfer signa
0
0 to 5 min 59 sec
E to N PreX (31G)
31M
Normal to Emergency
post-transfer signal
0
0 to 5 min 59 sec
N to E PosX (31M)
31N
Emergency to Normal
post-transfer signal
0
0 to 5 min 59 sec
E to N PosX (31N)
Inphase
inphase transfer
0
0 to 3 sec
Inphase
Fail accept
maximum
failure to accept
Emergency source alarm
0
0 to 6 sec
see NOTICE below
E Accept Fail