NRT405F902

2

Occupancy detection

Parameter 3 determines if the DI is window contact input or 
occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode.

Setpoint

The setpoint is set using the INCREASE and DECREASE buttons. 
Parameter 24 determines what is shown in the display. Refer to the 
parameter list for details. 

Setpoint limitation

In parameters 34 and 35, it is possible to set the maximum allowed 
setpoint increase and decrease respectively. 
Example: If P35=5 and P34=3, the setpoint can be changed between 
17°C and 25°C (see the picture below).
The basic setpoint can be changed in parameter 64 (factory 
setting=22°C).

Figure 3: Example of setpoint limitation

Fan control

The fan can be controlled via NRT405F902 with the following modes: 
Low speed, Medium speed, High speed, Auto. The current fan speed 
in the Auto mode depends on the heating or cooling demand and the 
settings for each speed. 
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30. If 

the parameter is set to 1, the first fan speed step will be used for fan 

control. 
Via parameter 31, it is possible to set the fan to the lowest speed 
level when Auto mode is selected. If this parameter is set to 1, the fan 
will run in all operating modes except Off and Window (unless mould 
protection is active, in which case the fan will run in these modes as 
well).

Manual control of the fan speed

By pressing the fan button, you change the fan speed according to 
the sequence I

à

II

à

III

à

AUTO. When using manual control, ”MAN” is 

shown in the display.

If the fan has been configured not to be affected by the heating or 

cooling demand, ”AUTO” will not be shown when pressing the fan button.

Indications

The display has the following indications:
HEAT   Heating control
COOL   Cooling control

       The open window symbol is shown if this function has  

 

been configured and a window is open. 

OFF   The controller does not heat or cool

On/Off button

By pressing the On/Off button, NRT405F902 will switch between Off 
mode and Comfort/Economy mode.

Parameter list

When the controller is in Comfort mode or Window mode, different param-
eter values can be set in a parameter list. 
Hold the INCREASE and DECREASE buttons depressed simultaneously 
for about 5 seconds until the Service symbol is displayed and then press 
the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and DE-
CREASE buttons to scroll between the parameters and press the On/Off 
button to select the desired parameter. The parameter number will then 
be replaced by the parameter value. The value can be changed using the 
INCREASE and DECREASE buttons. If a button is held depressed the 

value will start scrolling, first slowly and then with increasing speed.

To exit the parameter list and go back to the basic display, press the IN-
CREASE button until “EXIT” is shown (one step before parameter 1) and 
press the On/Off button. You can also exit the parameter list by pressing 
down the INCREASE and DECREASE buttons simultaneously.

Parameters

The following parameters can be changed in the parameter list.

Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed

Description

FS

1

Control mode:
2=2-pipe system 
3=4-pipe system 

 

4=Electric heater 

(not used for this model)

3

2

Change-over mode: 
0=Heating control, 1=Cooling control, 2=Automatic 
change-over depending on analogue temperature 
sensor or digital input

2

Description

FS

3

Operating mode when activating digital input 1:
0=Economy mode (occupancy detector)
1=Off mode (window contact)

0

4

Mould protection:
0=Not active
1=Active (fan never stops)

0

5

Neutral zone at Comfort mode (NZC). If the neu-
tral zone is 2 K, the heating setpoint equals the 
setpoint minus 1 and the cooling setpoint equals 
the setpoint plus 1.

2 K

6

Heating setpoint when unoccupied.

15°C

7

Cooling setpoint when unoccupied.

30°C

8

P-band for the room controller.

10 K

9

I-time for the room controller.

300 s

10

Not used for this model

11

Switch off timer for Comfort mode.

0 min

12

Switch on delay for Comfort mode.

0 min

13

Sensor connected to AI1:
0=Internal sensor, 1=External room sensor

0

14

Sensor connected to UI1:
0=None, 1=Change-over digital, 2=Change-over 
analogue

0

15

Not used for this model

16

Output signal for actuator connected to AO1: 
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V

0

17

Output signal for actuator connected to AO2: 
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V

0

18-
21

Not used for this model

22

Time in hours between exercise of heating actua-
tor.

23

23

Time in hours between exercise of cooling actua-
tor.

23

24

Setpoint or actual value shown in the display: 
0=Actual, setpoint when changing the setpoint, 
1=Actual, setpoint adjustment when changing the 
setpoint, 2=Setpoint, 3=Only the setpoint adjust-
ment

2

Содержание NRT405F902

Страница 1: ... the bottom plate The bottom plate with terminals has a number of hole combinations Select suitable holes and fasten the bottom plate on the wall or connection box so that the arrows on the bottom plate point upwards Do not tighten the screws too hard Disconnection NRT405F902 should be connected to a switch or circuit breaker in the building installation This switch should be in close proximity to...

Страница 2: ...y for about 5 seconds until the Service symbol is displayed and then press the INCREASE button twice First the display will show parameter 1 Use the INCREASE and DE CREASE buttons to scroll between the parameters and press the On Off button to select the desired parameter The parameter number will then be replaced by the parameter value The value can be changed using the INCREASE and DECREASE butt...

Страница 3: ... NC universal input 1 0 NO 1 NC 0 38 Not used for this model 1 39 Not used for this model 1 40 Manual Auto heating output signal 0 Off 1 Manual 2 Auto 2 41 Manual Auto cooling output signal 0 Off 1 Manual 2 Auto 2 Nº Description FS 42 Heating output signal in manual mode 0 43 Cooling output signal in manual mode 0 44 Model 45 Version Major 46 Version Minor 47 Released or beta version 48 Revision 4...

Страница 4: ...ol per applicazioni versione 1 3 1 05 o successiva scaricabile dal sito Web di SAUTER ITALIA SPA www sauteritalia it Dati tecnici Tensione di alimentazione 230 V CA 10 50 60 Hz Consumo energetico 3 W Temperatura ambiente da 0 a 50 C Umidità ambiente Max 90 UR Temperatura di conservazione da 20 a 70 C Sensore di temperatura integrato Tipo NTC intervallo da 0 a 50 C Ingressi Fare riferimento alle il...

Страница 5: ...nte Comfort viene visualizzato nel display Riscaldamento e raffreddamento presentano una zona neutra NZC Un rilevatore di presenza può essere collegato al DI per scegliere tra Comfort ed Economy La commutazione tra Comfort Economy e Disattivazione può essere eseguita anche tramite il pulsante On Off Comfort Economy si seleziona tramite l elenco dei parametri Economy Standby Standby viene visualizz...

Страница 6: ...ale per il regolatore temperatura ambiente 10 K 9 Tempo di integrazione per regolatore temperatura ambiente 300 s 10 Non usato per questo modello 11 Timer di spegnimento per la modalità Comfort 0 min 12 Ritardo di accensione per la modalità Comfort 0 min 13 Sensore collegato a AI1 0 Sensore interno 1 Sensore ambiente esterno 0 14 Sensore collegato a UI1 0 Nessuno 1 Commutazione digitale 2 Commutaz...

Страница 7: ... indirizzi alle impostazioni predefinite 1 Impostazioni di fabbrica Modbus 9600 0 64 Setpoint di base Valore regolabile da 5 a 50 C 22 C Cablaggio 10 20 30 LOGIC 40 50 POWER Figura 4 Collegamenti della piastra di fondo da 0 a 10 V da 0 a 10 V B 230 V CA Commutazione 230 V CA 230 V CA 230 V CA da 0 a 10 V Figura 5 Schema di collegamento 10 L Linea 230 V CA Alimentazione elettrica 11 Non collegato 1...

Страница 8: ...ischer Erkennung Umschaltung oder BACnet MS TP Modbus 8 Bits 1 oder 2 Stoppbits Ungerade gerade WE oder keine Parität Komm geschwindigkeit 9600 19200 38400 bps Modbus und BACnet oder 76800 bps nur BACnet Klemmenblöcke Lift Typ für Kabelquerschnitte bis zu 2 1 mm2 Schutzart IP20 Verschmutzungsgrad 2 Überspannungskategorie 3 Material Gehäuse Polykarbonat PC Abmessungen 102 x 120 x 29 mm Installation...

Страница 9: ...dieser Parameter auf 1 gestellt wird wird nur die erste Ventilatorstufe zur An steuerung verwendet Mit Parameter 31 kann eine Grundstufe für den Ventilator bei Auto eingestellt werden Wenn dieser Parameter auf 1 gestellt wird läuft der Ventilator in allen Betriebsmodi außer dem Abschaltbetrieb und Fenster bei aktivierter Schimmelschutzfunktion läuft der Ventilator trotzdem weiter Manuelles Einstel...

Страница 10: ...ntilatorstufe in Auto 0 Folgt dem Heiz Kühlstellsignal 1 Ventilatorbetrieb mit Grundstufe 1 32 Temperaturkorrektur an AI1 0 K 33 Temperaturkorrektur interner Raumfühler 0 K 34 Max SW Erhöhung bei Anpassung Einstellbarer Wert 0 13 K Basis SW 22 C 13 K 35 Max SW Senkung bei Anpassung Einstellbarer Wert 0 17 K Basis SW 22 C 17 K 36 NO NG Digitaleingang 1 0 NO 1 NG 0 37 NO NG Universaleingang 1 0 NO 1...

Страница 11: ...pour les produits ayant la version 1 2 ou plus Veuillez lire cette instruction avant de procéder à l installation et au raccordement du produit NRT405F902 FR Afin d éviter tout risque d incident ou d accident veillez à respecter les conseils de sécurité donnés dans cette notice et identifiés par ce symbole Régulateur d ambiance pour le contrôle de ventilo convecteurs NRT405F902 est un régulateur d...

Страница 12: ...e et de refroidissement sont réglables indépendamment Ré glages usine consigne de chauffage 15 C et consigne de refroidisse ment 30 C Arrêt Off Le régulateur ne commande ni le chauffage ni le refroidisse ment et le ventilateur est à l arrêt sauf si la protection anti moisissure a été sélectionnée Dans ce cas le ventilateur continue de tourner Fenêtre est affiché à l écran le régulateur est en mode...

Страница 13: ...ur de consigne du chauffage en mode Éco 15 C 7 Valeur de consigne du refroidissement en mode Éco 30 C 8 Bande proportionnelle du régulateur 10 K 9 Temps d intégration du régulateur 300 s 10 Sans objet pour ce modèle 11 Délai de mise à l arrêt du mode Confort 0 min 12 Délai de mise en route du mode Confort 0 min 13 Type de sonde raccordée à AI1 0 Sonde interne 1 Sonde d ambiance externe 0 14 Type d...

Страница 14: ...signal de sortie refroidissement 0 44 Modèle 45 Version Majeure 46 Version Mineure 47 Version officielle ou bêta 48 Révision 49 Rétroéclairage afficheur faible luminosité 10 50 Rétroéclairage afficheur luminosité élevée 30 51 Adresse PLA 52 Adresse ELA 53 Adresse Modbus 254 54 Bit de parité pour la communication Modbus 0 Pas de parité 1 Parité impaire 2 Parité paire 2 55 Déconnexion automatique Mo...

Страница 15: ... 50 Agnd Commun signaux analogiques 51 AO1 Sortie analogique 1 52 AO2 Sortie analogique 2 53 A RS485 communication A 54 B RS485 communication B Protection par fusible équivalent à la somme des courants entre DO1 DO3 Directive basse tension BT Directive compatibilité électromagnétique CEM Ce produit est conforme aux exigences des directives CEM et BT et répond aux standards EN60730 1 2000 et EN6073...

Отзывы: