SAUTER
flexotron®400 - RDT405
Configuration
P100012100
23
8.1.3
Menus X.3
P-band
Here you set the P-band (Proportional band) The P-band unit depends on the
choice of control mode. The P-band is the control offset necessary to drive an
output signal from 0 to 100%. In configurations involving two outputs the same P-
band applies to both outputs.
8.1.4
Menus X.4
I-time
Here you set the Integration time (Reset time). If the I-time is set to 0 the
integration function is disabled and the controller will act as a P-controller.
8.1.5
Menu 1.5
Damper minimum position (Control mode 1 only)
If you in menu 1.1 have configured output AO2 to be a damper, alternative 6 or 7,
you can set a minimum value to the damper signal. . The damper output will then
not go lower than the set value during normal operation. On shut-down however
the signal will go to zero and fully close the damper.
8.1.6
Menu 2.5
Output min./max. limiting (Control mode 2)
The output can be min./max. limited. The minimum value can be set between
0…99% and the maximum value between 1…100%. If min./max. parameters are
accidentally set to overlap one another, the max. function will be disabled and the
output will assume control.