Addressing the room operating units on the wireless controller 

When the system is put into operation for the first time, the radio connection must be set up between 

the room operating unit and the wireless controller. Addressing is not lost when batteries are replaced. 

After the desired channel (one or more) has been selected on the wireless controller, the 'OK' and 

'Escape' buttons must be pressed for 5 s. 'Pair' appears briefly on the display, denoting that the con-

nection between the thermostat and the controller has been established. 

To test the connection, these two buttons can be pressed again for 5 s. During the 5 s, 'Pair' briefly 

lights up on the display, followed by 'Test', along with the relevant channel LED on the controller. 

After the addressing, the time and date must be entered as follows: hours, minutes, year, month and 

day. The '+' and '-' buttons are used to change the values, and each step should be confirmed with the 

'OK' button. When the time has been entered in the first room operating unit, this time is forwarded to 

all room operating units in the system (master controller to slave controller). If the time has not been 

entered on the first addressed unit, this is queried on the next unit. If the 'OK' button is pressed for 10 

s, the time and date can be called up and changed. An automatic summertime/wintertime change-

over is stored. This can be deactivated in service mode using parameters. 

 

Basic functions 

After the addressing, the device switches to sleep mode after 10 s. The display shows the actual 

temperature, the radio transmission, the ECO symbol, the day and, if the battery is low, the battery 

symbol. Pressing any button switches the device on, and the device obtains the current data from the 

wireless controller. The unit must be switched on before any entry, parameterisation or function 

change can be made. 

The setpoint can be set by pressing the '+' or '-' button again. After 5 s, or immediately after the 'OK' 

button is pressed, the selected setpoint is automatically sent to the wireless controller and saved 

there. After that, the actual temperature value is retrieved every 10 minutes. 

By pressing the 'Menu' button again, it is possible to switch between the frost protection mode (Off), 

ECO, normal operation or the time programme. If the room operating unit is configured so that 

change-over between heating and cooling was programmed, these two modes are also available. 

The button lock is activated by pressing the '+' and '-' buttons for 5 s. The 'button lock' symbol appears 

on the display, also in sleep mode. The lock is removed by pressing both buttons again for 5 s. 

If the 'Menu' button is pressed again for 5 s, the display shows the first level of the parameter settings. 

If the 'Menu' button is briefly pressed again, the parameters up to P-SE, parameters of the service 

level, are shown. 

 

Time programmes 

Stored in the wireless controller are three time programmes that can be altered using the wireless 

room control unit. Whenever a time programme is altered, it is adopted by all the other room operating 

units that use the same profile. 

 

Time programme I: 

A profile for all days of the week; three switching points are available. Time programme I includes only 

one profile; the profile is identical for every day. 

 

Time programme II: 

A profile for the working days of Monday to Friday and a profile for the weekend. Three switching 

points are available for all working days, and three additional switching points are available for the 

weekend. 

 

Time programme III: 

A profile for every day; three switching points are available for each day. With time programme III, you 

can choose different profiles for each day. 

 

A switching point always consists of two change-over points. A time must be specified for each 

change-over point. For the first change-over point, the time for the change from 'Reduced Mode' to 

'Normal Mode' is set. For the second change-over point, the time for the switch from 'Normal Mode' to 

'Reduced Mode' is set. 

 

7145016003  01 

Содержание LRA 4 Series

Страница 1: ...RA420R K124 black LRA450R K104 white 5 95 LRA450R K124 black 5 95 Setting range 5 30 C Perm ambient temperature 0 55 C Setting accuracy 0 1 K Perm ambient humidity 5 80 rh Sensor NTC 10 kΩ Weight 0 13 kg Humidity accuracy 3 5 rh at 55 rh 23 C Hysteresis average 3 rh Ingress protection IP 20 EN 60529 Protection class III EN 60730 Radio frequency 868 3 MHz CE conformity as per Transmission power 13 ...

Страница 2: ...control is possible without any additional settings If a cooling command is entered on the controller via the C O input cooling control starts automatically The cooling symbol is displayed on the room operating unit Other applications such as cooling via the master room operating unit and special function settings for hotels or public buildings can be set by means of the service parameters Enginee...

Страница 3: ... by pressing the or button again After 5 s or immediately after the OK button is pressed the selected setpoint is automatically sent to the wireless controller and saved there After that the actual temperature value is retrieved every 10 minutes By pressing the Menu button again it is possible to switch between the frost protection mode Off ECO normal operation or the time programme If the room op...

Страница 4: ...odes frost protection reduced operation normal operation time programme heating or cooling Select parameter menu mode Change setpoint Save value Confirm selection Change time Cancel Addressing Test addressing Lock unlock manual operation Select function or display directly Function Heating or cooling party function has priority over all other functions Over ride is active for the time set here bet...

Страница 5: ...ated humidity sensor 65 55 P SE Service parameters The service parameters are protected by a password set at 1 2 3 4 at the factory Parameter P SE comes after parameter P 11 If the OK button is pressed the code is queried Each number must be confirmed by pressing OK The first service parameter is P 20 If you press the OK button you are taken to the P 20 parameter list Pressing the Escape button ta...

Страница 6: ...ireless room operating unit 0 Parameters that are specific to the installation and the topology Factory setting P 51 Set priorities for the heating cooling change over and for the heating cooling output or burner control 0 P 52 Activate or deactivate the Optimised time programme function 0 deactivated P 53 Set the type of communication between wireless controllers options radio or bus 0 Control pa...

Страница 7: ...LRA4 45 016 7 Sauter Components Cover plate Outside temperature sensor Printed in Switzerland Subject to changes Fr Sauter AG CH 4016 Basle 7145016003 01 ...

Отзывы: